INSTALLATION AND OPERATION INSTRUCTIONS

HotPod

TM

MODELS: EHP6-10002CT

                  EHP8-14402CT

INSTALLATION REQUIREMENTS

Follow All State and Local Codes.

•  Each HotPod

TM

 must be supplied with a dedicated 120 volt AC circuit, 15A for 1000W models, 20Amp for 1440W    

models.  Use 14 ga. copper wire

 MINIMUM

.

•  For indoor use ONLY with 6” or 8” round ductwork   (depending on model).

•  Units are rated for zero clearance.

CHOOSE LOCATION (Figure 1)

1.  Install HotPod

TM

 in a horizontal position ONLY.

2.  Select a 14” (35.6 cm) section of duct that is a 

MINIMUM

 of 4 feet (122 cm) from outlet register.

•  Select section so that you can insert male crimped end into inlet side of the HotPod

TM

.

• 

Discharge end must point toward outlet register (arrows show air flow direction).

•  Position wiring enclosure to allow permanent access to the wiring compartment.

INSTALL HotPod

TM

1.  Remove 9” (22.9 cm) section of duct for the 6” HotPod or 9 1/2” for the 8” HotPod. Allow an additional 5” (12.7cm) for 

the optional 

Silent Boot.

 

For Rigid Metal Duct

•  Crimp ends of the duct as needed to provide male ends for insertion into the HotPod

TM.

•  Fasten with a minimum of 3 sheet metal screws at both ends and within 1.5” (3.8 cm) of the end of the housing.  Seal 

with a good quality duct tape.

 

For Flexible Duct

• 

Attach flexible duct directly to HotPod

TM 

housing using approved connection methods.

Patent No’s.:

US  8,285,127;

 8,625,976;

 8,787,738:

 

8,837,922     

INSTALLATION

INSTRUCTIONS

 

Содержание HotPod EHP6-10002CT

Страница 1: ...that you can insert male crimped end into inlet side of the HotPodTM Discharge end must point toward outlet register arrows show air flow direction Position wiring enclosure to allow permanent access to the wiring compartment INSTALL HotPodTM 1 Remove 9 22 9 cm section of duct for the 6 HotPod or 9 1 2 for the 8 HotPod Allow an additional 5 12 7cm for the optional Silent Boot For Rigid Metal Duct ...

Страница 2: ...R PERMANENT WIRED MODELS 1 Remove wiring cover Following all local codes connect to 120 Vac 15 amp dedicated circuit for 1000w models and 120 Vac 20amp dedicated circuit for 1440w models Provide strain relief for all wiring A Black hot wire to L1 terminal See Fig 2 B White neutral wire to NEUT terminal See Fig 2 C Green or ground wire to green housing ground screw CORD CONNECTED MODELS For cord co...

Страница 3: ...hermostat cable approximately 3 1 2 inches from stripped end Using a pair of pliers press firmly onto cable and into double d shaped hole provided in control board enclosure THERMOSTAT INSTALLATION FOR HARD WIRED THERMOSTATS Note All thermostats may not operate the HotPod correctly The thermostat must operate the fan with the heat Fig 3 R W W2 Y G C 2 5 RED R HOT WIRE WHITE W1 HEAT GREEN Y G FAN B...

Страница 4: ...s from the system through the opening in wall plate Wiring must not interfere with the operation of the thermostat 6 Connect the wires to the proper terminals See Fig 3 7 Once you have finished installing the thermostat in the desired location restore power to the Hotpod 8 Refer to instructions included with the thermostat for setup and operating details THERMOSTAT SETUP INSTRUCTIONS Once you have...

Отзывы: