background image

Thank you very much for purchased Tozen products. 
Please read the Instruction Manual before use to ensure using this product in correctly and safely 
way. 
 
The definition of the symbol use in the text as below shown: - 

!  

Warning 

:   If did not implement protection measure,  may result in death or 

seriously injury. 

!  

Caution  

:    If did not implement protection measure,    may cause minor injury or 

parts damaged. 

Contents 

1.

Application 

2.

Specification 

3.

Operation 

4.

Installation 

 

4.1

 

Installation Example 

 

4.2

 

Precaution 

    4.3

 

Installation Space 

5.

Operation Manual 

    5.1

 

Precaution 

    5.2

 

Procedure 

6.

Maintenance Manual 

7.

Cause & Counter Measure Of Malfunction 

8.

Sizes Selection Diagram Sizes Selection Diagram & Pressure Reducing Valve (When Pilot 
Valve Fully Open) Flow Chart 

 

1.

Application 

     

Building equipment, air-conditioning equipment, factory equipment, irrigation facility, the 

water supply piping to reduce pressure on outlet or downstream side and maintain a certain 
range. 
 

2.

Specification 

Model PRV-CPR 

Sizes (mm) 

65

150 

Application Fluid 

Water, Warm Water 

Fluid Temperature 

5

60

 

Applicable Inlet Pressure 

Under 1.6MPa 

Max. Pressure Reduction Ratio 

10

Connection 

BS4504-3.2 PN16RF Flange (GB/T9113.1, EN1092-1)

Material 

 

Body FCD450 

Main Part 

Seat : SCS13A,    Diaphragm, Shield Ring : NBR 

Содержание PRV-CPR

Страница 1: ...20201203 PRV CPR Pressure Reducing valve Instruction Manual...

Страница 2: ...on Manual 5 1 Precaution 5 2 Procedure Maintenance Manual Cause Counter Measure Of Malfunction Sizes Selection Diagram Sizes Selection Diagram Pressure Reducing Valve When Pilot Valve Fully Open Flow...

Страница 3: ...of the diaphragmin the pilot valvepressure increase the discassembly of the pilot valve will rise and the pilot valve will closed Thepilotvalveclosed theupperpartofthediaphragminthePRVbodypressurewil...

Страница 4: ...y the surrounding and there is a risk to get hurt Caution Remove the foreign matters in the pipe line before install the valve The valve can t have the original performance and may damage if foreign p...

Страница 5: ...on failure Toavoidpipefreezing drainthepipewaterandthermalinsulationthepipe By freezing may damage the valve Pleasesecuretheinstallationspace referto4 3InstallationSpace When doing maintenance and ins...

Страница 6: ...terflow makesureallthepipeworkbeenproperinstalled If the water spouting off the pipe line it may dirty the surrounding and there is a risk to get hurt Caution Remove the foreign particles in the pipe...

Страница 7: ...er out from the valve body outlet side pressure become zero only can proceed If the water spouting off the pipe line it may dirty the surrounding and there is a risk to get hurt Caution To maintain th...

Страница 8: ...damaged Exchange the part Strainer clogging Clean the strainer mesh Outlet side pressure does not rise The valve body s stem can t operate smoothly Stem seat guide bush Use cloth file to filing the st...

Страница 9: ...s Selection Diagram Pressure Reducing Valve When Pilot Valve Fully Open Flow Chart Note Max 3m s flow speed Sizes selection diagram TRV P Pilot Valve fully Open Performance Flow Chart Flow rate Differ...

Отзывы: