tozen PRV-CPR Скачать руководство пользователя страница 7

If no happened abnormal, fully open the inlet side shut off valve, then fully open outlet 
side shut off valve. 

    ⑥

To setting outlet side pressure, open the upper cap of the pilot valve, checking the pressure 
gauge at outlet side, to let the setting pressure higher, turn the adjusting bolt clockwise, 
to lower the setting pressure, turn to anti clockwise. 

 
 
 
 
 

6.

Maintenance Procedures 

 
 
 
 
 
 
 
   
 
 
 
 
 
 
 
 
 
   

 

 

 
 

 
 

 
 
 
 
 
 
 
 
 
 
 

7.3 

分解図

 

!  

Warning

 

     

⦿

 

If want to dismantle the valve, close the Inlet side shut off valve, drain the water out 

from the valve body, outlet side pressure become zero, only can proceed. 

            ※

If the water spouting off the pipe line, it may dirty the surrounding and there is a 
risk to get hurt. 

!  

Caution

 

     

⦿

 

To maintain this product's function & performance, please perform daily checking and 

regular inspection. 

⦿

 

To dismantle the valve, please perform by the skilled specialist (facility contractor). 

            ※

If done by normal people, the valve may lost the adjusting function. 

!  

Caution

 

     

⦿

 

Other than main body have strainer, this product's needle valve at inlet side in the pilot tube 

also have strainer, if foreign matter stick to the strainer, please remove it.

 

            ※

If the strainer clogging, the valve may not function. 

Содержание PRV-CPR

Страница 1: ...20201203 PRV CPR Pressure Reducing valve Instruction Manual...

Страница 2: ...on Manual 5 1 Precaution 5 2 Procedure Maintenance Manual Cause Counter Measure Of Malfunction Sizes Selection Diagram Sizes Selection Diagram Pressure Reducing Valve When Pilot Valve Fully Open Flow...

Страница 3: ...of the diaphragmin the pilot valvepressure increase the discassembly of the pilot valve will rise and the pilot valve will closed Thepilotvalveclosed theupperpartofthediaphragminthePRVbodypressurewil...

Страница 4: ...y the surrounding and there is a risk to get hurt Caution Remove the foreign matters in the pipe line before install the valve The valve can t have the original performance and may damage if foreign p...

Страница 5: ...on failure Toavoidpipefreezing drainthepipewaterandthermalinsulationthepipe By freezing may damage the valve Pleasesecuretheinstallationspace referto4 3InstallationSpace When doing maintenance and ins...

Страница 6: ...terflow makesureallthepipeworkbeenproperinstalled If the water spouting off the pipe line it may dirty the surrounding and there is a risk to get hurt Caution Remove the foreign particles in the pipe...

Страница 7: ...er out from the valve body outlet side pressure become zero only can proceed If the water spouting off the pipe line it may dirty the surrounding and there is a risk to get hurt Caution To maintain th...

Страница 8: ...damaged Exchange the part Strainer clogging Clean the strainer mesh Outlet side pressure does not rise The valve body s stem can t operate smoothly Stem seat guide bush Use cloth file to filing the st...

Страница 9: ...s Selection Diagram Pressure Reducing Valve When Pilot Valve Fully Open Flow Chart Note Max 3m s flow speed Sizes selection diagram TRV P Pilot Valve fully Open Performance Flow Chart Flow rate Differ...

Отзывы: