Multi Variable Air Conditioners Floor and Ceiling Type Indoor Unit
Address 8, dial-up value 0111 Address 8, dial-up value 1010
3.7.3 Capacity Code
On the mainboard of indoor unit, two 4-bit DIP switches are used to distribute the address and capacity
of indoor units. The 4-bit DIP switch (marked with “capacity” below) used for setting the capacity of indoor
units is factory set before shipment of indoor unit, while it is covered by sealant, so that it cannot be changed
by the user.
Below is factory default setting:
The default Capacity dial-up is the maximum capacity of indoor unit. As shown above, the capacity is
(See above for the lever position)
Dial-up Value
The dial-up value of capacity code is set in binary system. The dial-up value is “0” when the lever is
dialed to “ON” end; the dial-up is “1” when the lever is dialed to numerical end on opposite side. For number
4~1 on the capacity code, the dial-up #4 refers to high bit and the dial-up 1# refers to low bit.
Dial-up Table (4-bit Dial-up Switch)
4-bit
4-bit
4-bit
1-bit
Capacity
0
0
0
0
20
0
0
0
1
25
0
0
1
0
30
0
0
1
1
35
0
1
0
0
40
0
1
0
1
45
0
1
1
0
50
0
1
1
1
60
1
0
0
0
224
1
0
0
1
70
1
0
1
0
80
1
0
1
1
90
1
1
0
0
100
1
1
0
1
112
1
1
1
0
140
1
1
1
1
280