8

Multi Variable Air Conditioners Floor and Ceiling Type Indoor Unit

from the wired controller directly. The remote control mode refers to that the indoor unit is controlled from 
remote controller. When the setting is remote control mode, its function dial-up must be set on S7.

Dial-up switch 3 (M/S): 

The setting of master / slave indoor unit refers to the master / slave setting of indoor run mode, mainly 

used to meet the needs of special people on priority (e.g. leader, patients, etc). The factory default setting is 
that all indoor units are master (dial-up switch pulled to “ON” position).

When all the indoor units are set as slave, the outdoor unit will run according to the mode of slave indoor 

unit that is firstly started. If the mode of slave indoor unit started later has in conflict against the mode started 
earlier, the system will display mode conflict error, so that the indoor unit started later cannot work. In this 
case, the run mode of the unit is decided by the slave indoor unit that is firstly started.

When only one indoor unit is set as master, no matter if the master indoor unit is firstly started or not, the 

slave indoor unit will give out mode conflict error as long as its mode is in conflict against the mode of master 

indoor unit (except that the master indoor unit is stopped). In this case, the unit run according to the mode of 
master indoor unit on priority.

When several indoor units are set as master, the mode of master indoor unit with a lower address code 

will be taken as the master run mode of the unit. when the master indoor unit with the lowest address code is 
changed from STOP state to RUN state, the mode of other master indoor units or slave indoor units shall be 

kept identical to its mode; otherwise the system will give out mode conflict error. Therefore, when there are 

several master indoor units, the address code of the unit shall be set from lower to higher according to priority 
level.

Dial-up switch 4 (I/O): 

Setting of ambient temperature acquisition point. This setting is mainly used when the temperature of air 

conditioner area differs largely from the air inlet temperature of the unit. Meanwhile, this setting is only valid 
when the receiver is connected, including the setting of temperature acquisition point at air inlet and setting 
of the temperature acquisition point at receiver head. The factory default setting is acquisition of air inlet 
temperature (dial-up switch pulled to “ON” position).

Dial-up switch 5 (L/H): Setting of high / low static pressure fan. This setting includes the setting of high 

static pressure fan and low static pressure fan, adjusted as needed for the project. The factory default setting is 
low static pressure fan (dial-up switch pulled to “ON” position).

Cautions:

1) The above settings must be done under power shutdown state.
2) When the “setting of control mode” is “L”, the function dial-up for “setting of memory mode” and 

“setting of master / slave indoor unit” will be disabled. When the “setting of control mode” is “I”, this function 
dial-up setting is enabled.

3) The dial-up switch shall be put to position correctly, and shall not be put to middle position. Dialing of 

the switch to “ON” position indicates “0” and the dialing to opposite direction indicates “1”.

4) After dialing up, please mark the address code of the unit(√).

3.7.2 Address code

Address dial-up must be set for the multi indoor units; otherwise the abnormal communication will be 

caused to the unit. The address code has 4-bit dial-up in total. The highest address is 16 and the lowest address 
is 1.

Содержание TGS-112CFTA-E

Страница 1: ...tioners Floor and Ceiling Type Indoor Unit Please read this manual carefully before using this product and keep it properly for future reference Models TGS 28CFTA E TGS 36CFTA E TGS 50CFTA E TGS 71CFT...

Страница 2: ...top At this time change the operation mode of the indoor unit to the one that would not clash with the outdoor operating mode to make the operation normal The cooling mode is not clash with the dry mo...

Страница 3: ...llation of the Unit 2 3 2 There are 2 Styles of Installation 3 3 3 In Case of Hanging 4 3 4 Electrical Wiring 5 3 5 Install the Drainage Pipe 6 3 6 Install the Connection Pipes 6 3 7 Dial up of Unit 7...

Страница 4: ...s may shortened Do not mangle wire or adopts wires that are not recommend to use otherwise electric shock or fire may happened Please don t operate the unit by wet hand or electric shock may happened...

Страница 5: ...oom Such a place where is condensation water is easily drained out Such a place that can handle the weight of indoor unit Such a place which has easy access for maintenance Such a place where is permi...

Страница 6: ...edure bellow Press the fixing knob of the air intake grills the grilles will be opened wider and then pull them out from the indoor Remove the side panel fixing screw and pull to the front direction a...

Страница 7: ...bracket opening Refer to Fig 8 3 3 In Case of Hanging It is possible to install using inward facing hanger brackets by not removing the brackets from the indoor unit Refer to Fig 9 Be sure to use only...

Страница 8: ...e piping hole of the chassis and the bottom of the appliance upward then connect the live wire to the Terminal board L neutral wire to the Terminal board N and connect the earthing wire to the screw t...

Страница 9: ...wards at a gradient of at least 1 100 to prevent air pockets Refer to Fig 12 Use the attached drain hose and clamp Insert the drain hose completely into the drain socket Tighten the clamp within the r...

Страница 10: ...low static pressure fan Low static pressure L High static H Functional description of function dial up Dial up switch 1 S R Setting of memory mode including the standby mode and restoration mode The...

Страница 11: ...or units or slave indoor units shall be kept identical to its mode otherwise the system will give out mode conflict error Therefore when there are several master indoor units the address code of the u...

Страница 12: ...The dial up value of address code is set in binary system The dial up value is 0 when the lever is dialed to ON end the dial up is 1 when the lever is dialed to numerical end on opposite side For numb...

Страница 13: ...t setting The default Capacity dial up is the maximum capacity of indoor unit As shown above the capacity is See above for the lever position Dial up Value The dial up value of capacity code is set in...

Страница 14: ...KING TEMPERATURE RANGE Working Temperature Range Indoor side state Outdoor side state Dry bulb temp C Wet bulb temp C Dry bulb temp C Wet bulb temp C Rated Cooling 27 19 35 24 Max cooling 32 23 43 26...

Страница 15: ...te control with dry cloth or a vacuum cleaner If damp cloth is used remove moisture by using dry cloth afterward Caution Do not use benzene gasoline thinners or polishing products for cleaning Do not...

Страница 16: ...r close glass windows when cooling to prevent heat load from sun light which may cause more electricity cost To distribute cool air throughout the room adjust airflow direction as shown by the arrows...

Страница 17: ...ause damage or personal injury Also pay special attention when children are around Do not channel the airflow directly at people especially infants aged persons or patients Turn off the air conditione...