– 22 –
TROUBLESHOOTING GUIDE
OVERHEAT PREVENTIVE RELAY(OHR)
Phenomenon
OHR works
Gas leakage
OHR is defective
Cause
1
2
compressor
OHR
NO
Any gas leakage?
YES
Firstly cut down power source. when the temp. of above part of the
compressor is below 50
°
C, does the OHR have electric continuity?
(see left fig)
NO
See trouble shooting (compressor)
YES
After repair, fill up prescribed gas.
attention high
temp.
Change OHR
1
2
3