OPERATION DETAILS
+3.7
30˚C
35˚C
15˚C
MAX
★
1
MAX
★
1
MIN
★
2
MIN
★
2
+4.7
0
Hz
Super
Low
Frequency of
compressor
Designate Fan blow
Low
Low or Super low
Designated Fan blow
Designated
temperature
Room temperature
Stop
Temperature,
indoor heat
exchanger
Indoor fan
★
1
110Hz
112Hz
★
2
24Hz
10Hz
TAN/TAG-A28EWI, TAN/TAG-A32EWI
TAN/TAG-A53EWI
HEATING MODE OPERATION
•
The compressor will stop when operational frequency reached the minimum frequency and that condition has
been kept for 6 minutes and the room temperature becomes 4.7
℃ higher than it
was set.
•
The compressor will re-start when room temperature becomes 3.7
℃
higher than
it
was set.
•
The operational frequency will be set every 80 seconds of operation.
The operational frequency setting will be calculated based on the deviation of the room temperature and the
set temperature on one end and the deviation factor at the time of previous setting on another.