3. OPERATION

BEFORE OPERATION:

LCDI (Leakage Current Detection and Interruption) PLUG

TEST: WHEN  CURRENT  LEAKING  OR 

PRESSING  TEST  BUTTON,  THE 
INDICATOR LIGHT WILL TURN OFF 
AND THE UNIT WILL CUT OUT.

RESET: AFTER  SOLVING  THE  PROBLEM 

PLEASE PRESS RESET BUTTON.

ALWAYS: MAKE SURE THE INDICATOR LAMP IS ON AFTER 

PLUGING INTO THE POWER. IF NOT, PRESS RESET 
BUTTON UNTIL IT CLICKS AND INDICATOR LAMP 
COMES ON.

HARD TO RESET BUTTON:
PRESSING BUTTON WITH A STICK SUCH AS PENCIL OR BALL 
POINT PEN WITH THE FLAT END (NOT SHARP EDGE) MAY MAKE 
IT EASIER TO RESET BUTTON.
NO POWER ON THE UNIT: MAKE SURE THE INDICATOR LAMP IS ON.

OPERATING STEPS:
1. PRESS  ‘’POWER’’ BUTTON (C1) TO ‘’ON’’.

Cool mode lamp (C7) and Low lamp are lit at this time and unit 
starts.

2. PRESS

 MODE BUTTON (C2).

Press  the  mode  button  (C2)  to  set  your  desired  operation 
mode “Cooling” (C7), “Dehumidify” (C8), “Fan” (C9).

Cooling mode (C7)

When  cool  mode  is  selected,  " "  will  show  in  the  LCD  Dis 

play, During the cooling mode the air is cooled and hot air is 
exhausted to the outside through the exhaust tube. Adjust fan 
speed and air temperature to suit your desired comfort level.

Note: The air exchange hoses must vent room when using 

cool mode.

Dehumidify mode (C8)

When Dehumidify mode is selected, " " will show in the LCD 

Display. Air is dehumidified as it passes through the unit, with-
out being in full cooling mode.
If  room  temperature  is  higher  than  25  degree  Celsius,  fan 
speed can be adjusted; otherwise fan speed is fixed to “Low “.

Note:  If  the  unit  is  to  be  used  as  a  dehumidifier,  do  not 

connect the exhaust hose let the warm air return to 

the room.

Continuous drainage is then necessary.

Fan mode (C9)

When  fan  mode  is  selected,  "

" will  be  shown  in  the  LCD 

Display, Air is circulated throughout the room with no cooling.

Note: The unit does not need to be vented in Fan mode.

3. PRESS TIMER/TEMPERATURE ADJUST BUTTONS (C5)

Set  the  desired  room  temperature  by  pressing  +  button  or  – 
button. The default display is room temperature.
When “+” or “– “ button is pressed, the set temperature is dis-
played and may be adjusted. After 15 seconds the display will 
revert back to room temperature.
By  pressing  both  “+”  and  “–”  buttons  at  the  same  time  for 
more than 3 seconds, the display will toggle between Celsius 
and Fahrenheit.

4. PRESS FAN SPEED BUTTON (C3)

Press the fan speed button (C3) to set the desired air flow rate.

........ Operation at a high air flow

......... Operation at a medium air flow

.......... Operation at a low air flow

5. AIR DEFLECTION

The  vertical  louvers  may  be  set  on  right  and  left  manually  in 
desired direction. (Fig. E)

6. STOP OPERATION

Press the Power button (C1) and all lights will go out.

TIMER OPERATION

Auto turning OFF:

With machine in running mode, press timer button for setting 
timer control. Press “+” or “–” to select number of hours you 
would like the unit to run before it automatically shuts off.

Auto turning ON:

With machine in stand by mode, press timer button for setting 
timer control. Press “+” or “–” to select number of hours be-
fore  the  unit  automatically  starts  running  in  air  conditioning 
mode.

Note : The time is adjustable between 1~24 hours.

USING REMOTE CONTROL

The functions work the same as your air conditioner’s opera-
tion panel. (Fig. C) All key functions can be accessed from the 
remote con trols.
Batteries: Remove the cover on the back of the remote control 
and insert the batteries with the (+) and (-) poles pointing in the 
proper direction. (Fig. H)

NOTE:

  ●

Do not drop the remote control.

  ●

Do not place the remote control in a location exposed to direct 
sunlight.

  ●

The  remote  control  should  be  placed  about  1  meter  or  more 
away from TV, or any other electrical appliances.

CAUTION

  ●

Use only AAA or IEC R03 1.5V batteries.

  ●

DO NOT attempt to recharge the supplied batteries. All batter-
ies should be replaced at the same time.

  ●

DO NOT dispose of the batteries in a fire as they may explode.

  ●

DO NOT install the batteries with the polarity (+/-) reversed.

  ●

Keep batteries and other things that could be swallowed away 
from young children. Contact a doctor immediately if an object 
is swallowed.

4. DRAINING EXCESS WATER (Fig. F)

1.

Drain excess water from the tank by placing a pan under the 
drain water outlet. (Fig. F2)

2.

Remove the drain plug, and let the water drain into the pan.

3.

When the water stops draining out, replace the drain plug.

4.

Remove the pan of water.

5.

Operate the unit in Fan mode to dry the interior of the unit.
NOTE: Remove the drain water from the tank once a week.

5. CLEANING

CLEANING AIR INTAKE GRILLE (Fig. G)

1.

Clean the air intake grille (B7) once every two weeks.

2.

To remove the air intake grille (B7), pull the grille off.

3.

Remove the dust with a vacuum cleaner.

WARNING

  ●

DO NOT touch the evaporator. It may cause injury or damage.

CLEANING SURFACE

Clean the outside of the unit with a soft damp cloth.

CAUTION

  ●

NEVER use gasoline, solvents, chemical products or polish as 
they could damage the surfaces.

6. LONG-TERM STORAGE

At the end of each season, or when you do not plan to use your 
unit  for  an  extended  period  of  time,  the  following  procedures  are 
recommended.
1.

Run the unit 5 or 6 hours with only the ‘’FAN’’ (C9) mode oper-
ating in order to dry the inside.

2. Remove the drain water from the tank and unplug the unit.
3. Clean the unit.

Wipe off any dirt or dust on the unit with a soft damp cloth or 
a vacuum cleaner, and then wipe again using a soft dry cloth.

4. Clean the air intake grille (B7) and replace it.
5. Store the unit.

The  original  shipping  carton  is  the  best  place  to  store  your 
unit.  If  you  do  not  have  the  original  packing  materials,  cover 
the unit with a large plastic bag and store in a cool dry place.

CAUTION

  ●

ALWAYS store the unit in the vertical position.

  ●

DO NOT put heavy objects on top of the unit.

2

ENGLISH

RESET

TEST

Содержание TAD-T35

Страница 1: ...TAD T35 INSTRUCTION MANUAL ENGLISH P 1 MANUAL DE INSTRUCCIONES ESPA OL P 5 MODE D EMPLOI FRAN AIS P 9 PORTABLE AIR CONDITIONER ACONDICIONADOR DE AIRE PORT TIL CONDITIONNEUR D AIR DEPLACABLE...

Страница 2: ...A1 A3 A4 A2 A7 A5 A6 C10 F1 F2 B5 C11 C6 C12 C1 C7 C1 C3 C4 C2 C5 C8 C9 C3 C4 C2 C5 more than 20 in 50 cm more than 20 in 50 cm I6 I3 I1 I2 J2 J4 J1 J3 J3 J4 J2 for exhaust for exhaust for intake for...

Страница 3: ...1198 Base pan assembly Caster Float Micro switch Drain motor Compressor Rear fan motor Rear fan Capacitor C Rear FM Front fan motor Front fan Capacitor A Rear FM Main circuit board Capacitor B Compres...

Страница 4: ...hould be operated when the room temperature is between 61 F 16 C to 95 F 35 C If the room temperature is below 61 F 16 C ice may form on the coils If the room tem perature is above 95 F 35 C the compr...

Страница 5: ...hours you would like the unit to run before it automatically shuts off Auto turning ON With machine in stand by mode press timer button for setting timer control Press or to select number of hours be...

Страница 6: ...2 000 BTU h ASHRAE 128 standard 7 500 BTU h DOE 2017 standard DEHUMIDIFYING CAPACITY 26 7 C 60 0 43 gal h 1 65 L H POWER SOURCE Single Phase 115V 60Hz POWER CONSUMPTION 1 050 W OPERATING CURRENT 9 5 A...

Страница 7: ...ry in basis to your nearest autho rized dealer or distributor of TOYOTOMI WHAT YOU MUST DO FOR WARRANTY SERVICE You must return the defective Product or part to any authorized dealer or distributor of...

Страница 8: ...1 Luz de establecer temporizador C12 Luz de velocidad del ventilador Fig I PIEZAS CONDUCTO DE ESCAPE I1 Manguera escape I2 Rejilla de conector manguera I3 Boquilla de conector manguera Fig J EQUIPO DE...

Страница 9: ...efecto es la tem peratura de la habitaci n Cuando se presiona el bot n o se muestra la temperatura establecida y puede ser modi ficada Despu s de 15 segundos la pantalla volver a la tem 4 PULSE EL BOT...

Страница 10: ...unidad funciona in termitente mente Mal funcionamiento La temperatura am biental es muy alta o muy baja La manguera del con ducto de escape est bloqueada Contacte al vendedor Revise la manguera del co...

Страница 11: ...o modificar los t rminos de esta garant a limitada En algunos estados no se permiten limitaciones o exclusiones en cuanto a la duraci n de las garant as impl citas o no permi ten la exclusi n o la lim...

Страница 12: ...Voyant de mode de refroidissement C10 Lampe de temp rature de la pi ce temp rature C11 Enssemble de minuterie de la lampe C12 Vitesse de ventilateur lampe Fig I TUYAUTERIE DE SORTIE D EVACUATION I1 B...

Страница 13: ...re 25 degr s Celsius la vitesse du ventilateur peut tre ajust e sinon la vi tesse du ventilateur est fix e Low Remarque Si le dispositif est destin une utilisation en mode DEHUMIDIFY ne branchez pas l...

Страница 14: ...risquez d endommager le compresseur Avant de d placer ou de transporter l appareil v rifiez que le r servoir de condensat est vide 8 DEPISTAGE DES PANNES SYMPTOMES CAUSES SOLUTIONS Le dispositif ne f...

Страница 15: ...iode de DOUZE 12 MOIS effective la date de livrai son l acheteur au d tail d origine suivant les termes ci apr s CE QUI EST COUVERT Produit ou ses pi ces avec d fauts mat riels ou vices de fabrication...

Страница 16: ...New 04 19 Part No 22741193 TOYOTOMI CO LTD 5 17 Momozono cho Mizuho ku Nagoya 467 0855 Japan www toyotomi jp Printed in China...

Отзывы: