VENT RESTRICTOR
Fig. #43a
OPENING
The vent restrictor is located on the underside of the firebox top. The unit leaves the factory
with the vent restrictor wide open. The restrictor is built into the appliance for secondary air
flow adjustment. Adjustment enables tuning the airflow for optimum flame appearance and
performance for a wide variety of vent configurations.
Setting:
• determine the vent height
• determine the vent horizontal length
• from the chart determine the restrictor position
Refer to the chart in Fig. #43 for the correct position of restrictor for the vent configuration
of your installation. Restrictor positions are based upon lab tests. The ideal position may
vary slightly with installation.
Restrictor position is too closed if the flame has the following characteristics:
• Flame is excessively tall and lifting.
• Flame lacks movement.
• Flame soots.
Restrictor position is too open if the flame has the following characteristics:
• Flame height is low.
• Flame has excessive movement.
To adjust the restrictor:
• Loosen the screw holding the restrictor.
• Move the restrictor to its intended opening.
• Re-tighten the screw
WALL AND ROOF
TERMINATION
RESTRICTOR POSITION
Fig. #43
12'
10'
30'
40'
48'
6'
4'
2'
0'
8'
30'
18"
4'
20'
22'
18'
20'
FULLY OPEN
3" OPEN
2" OPEN
3/4" OPEN LP
10'
0'
1" OPEN NG
6'
8'
10'
12'
14'
16'
18'
20'
26
TC30_CE3 250313-44
Vent Restrictor Adjustment