- 24 -
tousek
/ EN_ST-80-M-S_05 / 25. 03. 2020
Error
possible reason
solution
Display: „Stop-button triggered“
stop-button not connected or not bridged
Stop-button (Kl. ) connect or bridge
> use status display for help
Display: „Photocell triggered“
photocell interrupted
check correct connection hence re-
move obstacle > use status dispaly
for help
Display: „Main closing edge triggered“
main safety edge interrupted or hot-wired
check correct connection hence re-
move obstacle > use status dispaly
for help
Display: „AR-System triggered“
boom ran into an obstacle or is too hard
to move
check adjustment of forces, remove
obstacle hence check if boom is
easy to move
Display: „photocell test negative“
interruption or hot-wired photocell
check correct connection hence re-
move obstacle > use status dispaly
for help
Display: „Low Voltage“
undervoltage
check supply line
Display: „search Master“
communication problem
check connection/transmission
Display: „search Slave“
communication problem
check connection/transmission
Display: „Slave OFFLINE“
message of Master control, if Slave con-
trol not in „ready for use“ mode
make Slave control „ready for use“
Display: „AR-System Slave“
Slave-barrier ran into an obstacle or is too
hard to move
check adjustment of forces, remove
obstacle hence check if Slave
boom is easy to move
No reaction when giving an impulse
no line voltage hence
safety fuse broken
check line voltage as well as safety
fuses.
error of transmitter/control device/impulse
button,
e.g. transmitter not programmed
check transmitter/control device,
e.g. program transmitter and
check battery
Control relays are switching but no
barrier movement
motor is in emergency release (unlocked) lock motor gearing
8. Error search