WX9 ASD Installation and Operation Manual
169
Free Unit Multiplication Factor (0 = off)
Program
Utilities
Display Parameters
This parameter provides a multiplier for the displayed speed value shown on the
EOI of the ASD.
This parameter may be used to display the rate that a commodity is being
processed by the driven load in process units (i.e., units/time).
Example:
An output frequency of 100 Hz would be displayed as 50 Hz if using
a multiplier of 0.5 for this parameter.
Note:
PID frequency-limiting parameters (i.e.,
,
,
, and
) are not affected by this setting.
Direct Access Number — F702
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 200.0
Units — Hz/UDU
Free Unit Selection
Program
Utilities
Display Parameters
The parameter sets the number of decimal places to be displayed during non-
Acceleration/Deceleration (Acc/Dec)
functions.
Settings:
0 — 1
1 — 0.1
2 — 0.01
Direct Access Number — F703
Parameter Type —
Selection List
Factory Default —
0.1
Changeable During Run —
Yes
Acceleration/Deceleration Unit Time Setup
Program
Utilities
Display Parameters
This parameter sets the number of decimal places to be displayed for
Acceleration/Deceleration (Acc/Dec)
functions.
Settings:
0 — 1
1 — 0.1
2 — 0.01
Direct Access Number — F704
Parameter Type —
Selection List
Factory Default —
0.1
Changeable During Run —
Yes
Prohibit Initializing User Parameters During Typeform
Initialization
Program
Utilities
Prohibition
This parameter Enables/Disables the ability to initialize user parameters during
a
Type Form
initialization.
Settings:
0 — Enabled
1 — Disabled
Direct Access Number — F709
Parameter Type —
Selection List
Factory Default —
Enabled
Changeable During Run —
Yes
CN8 Option Override Multiplication Gain
Program
Feedback
Override Control
If operating using the
CN8 Option
, this parameter provides a value to be used
in the event that
Setting
is selected for the
Multiplying Input Selection
).
Direct Access Number — F729
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — -100.00
Maximum — 100.00
Units — %
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......