132
WX9 ASD Installation and Operation Manual
PID Feedback Delay Filter
Program
Feedback
Feedback Settings
This parameter determines the delay in the ASD output response to the motor-
control feedback signal (signal source is selected at
PID Feedback Signal
Selection
(
)).
Direct Access Number — F361
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
PID Feedback Proportional Gain
Program
Feedback
Feedback Settings
This parameter determines the degree that the
Proportional
function affects the
output signal. The larger the value entered here, the quicker the drive responds
to changes in feedback.
Direct Access Number — F362
Parameter Type —
Numerical
Factory Default —
0.10
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 100.0
PID Feedback Integral Gain
Program
Feedback
Feedback Settings
This parameter determines the degree that the
Integral
function affects the
output signal. The smaller the value here, the more pronounced the effect of the
integral function on the output signal.
Direct Access Number — F363
Parameter Type —
Numerical
Factory Default —
0.10
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 100.0
PID Deviation Upper Limit
Program
Feedback
Feedback Settings
This parameter determines the maximum amount that the feedback may
increase the output signal.
Direct Access Number — F364
Parameter Type —
Numerical
Factory Default —
50.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 50.00
Units — %
PID Deviation Lower Limit
Program
Feedback
Feedback Settings
This parameter determines the maximum amount that the feedback may
decrease the output signal.
Direct Access Number — F365
Parameter Type —
Numerical
Factory Default —
50.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 50.00
Units — %
PID Feedback Differential Gain
Program
Feedback
Feedback Settings
This parameter determines the degree that the
Differential
function affects the
output signal. The larger the value entered here, the more pronounced the affect
of the differential function for a given feedback signal level.
Direct Access Number — F366
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 2.55
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......