WX9 ASD Installation and Operation Manual
131
Commercial Power/ASD Switching Frequency
Program
Terminal
Line Power Switching
When enabled, this parameter sets the frequency at which the
At Frequency
Powerline Switching
function engages.
The
At Frequency Powerline Switching
function commands the system to
discontinue using the output of the drive and to switch to commercial power
once reaching the frequency set here.
See
Commercial Power/ASD Switching Output Selection
for
additional information on this setting.
Direct Access Number — F355
Parameter Type —
Numerical
Factory Default —
60.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz
ASD-Side Switching Waiting Time
Program
Terminal
Line Power Switching
This parameter determines the amount of time that the drive will wait before
outputting a signal to the motor once the switch-to-drive-output criteria has
been met.
See
Commercial Power/ASD Switching Output Selection
additional information on this setting.
Direct Access Number — F356
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — (ASD-Dependent)
Maximum — 10.00
Units — Seconds
Commercial Power Side Switching Waiting Time
Program
Terminal
Line Power Switching
This parameter determines the amount of time that the drive will wait before
allowing commercial power to be applied to the motor once the switch-to-
commercial-power criteria has been met.
See
Commercial Power/ASD Switching Output Selection
additional information on this setting.
Direct Access Number — F357
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — (ASD-Dependent)
Maximum — 10.00
Units — Seconds
Commercial Power Switching Frequency Holding Time
Program
Terminal
Line Power Switching
This parameter determines the amount of time that the connection to
commercial power is maintained once the switch-to-drive-output criteria has
been met.
See
Commercial Power/ASD Switching Output Selection
additional information on this setting.
Direct Access Number — F358
Parameter Type —
Numerical
Factory Default —
2.00
Changeable During Run —
Yes
Minimum — 0.10
Maximum — 10.00
Units — Seconds
PID Feedback Signal Selection
Program
Feedback
Feedback Settings
This parameter Enables/Disables
PID
feedback control. When enabled, this
parameter determines the source of the motor-control feedback.
Settings:
0 — PID Control Disabled
1 — VI/II
2 — RR
3 — RX
4 — RX2
Proportional-Integral-Derivative
(PID) — A closed-loop control technique
that seeks error minimization by reacting to three values: One that is
proportional to the error, one that is representative of the error, and one that is
representative of the rate of change of the error.
Direct Access Number — F360
Parameter Type —
Selection List
Factory Default —
PID Control
Disabled
Changeable During Run —
Yes
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......