Air to Air Heat Exchanger

Installation Manual

EN

Air to Air Heat Exchanger

Installation Manual

1) When switching the remote controller between invalid/valid from an external device 

SW1 [Remote controller Invalid: ON, Valid: OFF]

• For NRC-01HE (remote controller for the Air to Air Heat Exchanger), when one of the buttons below is 

pressed, 

 blinks and the operation is invalid.

* [ON/OFF] button
* [VENT] button
* [VENT MODE] button
* [VENT FAN] button

• For RBC-AMT32E, AMS41E (remote controller for the air conditioner), pressing the [ON/OFF] button has 

no effect.

• When the remote controller is inoperable, the 24-hour ventilation mode and nighttime heat purge operation 

are not available.

• If a command is sent to one of the units in the group, the invalid/valid setting of the remote controller in the 

group can be switched.

2) When switching between low/high from an external device 

SW2 [Low: ON, High: OFF]

• For NRC-01HE (remote controller for the Air to Air Heat Exchanger), the message on the display is 

changed. However, when the air conditioner operates Air to Air Heat Exchanger system linked with air 
conditioners, ventilation fan speed (Low/High) is changed though the ventilation amount is not shown on 
the display.

• If a command is sent to one of the units in the group, all the Air to Air Heat Exchangers in the group operate 

together.

• The latter operation of the remote controller or the external device overrides the former.

(locally procured)

Remote ON/OFF Adapter NRB-1HE

CN705

Control circuit board of the 
Air to Air Heat Exchanger

SW1

As these terminals are not used, insulate them.

The remote controller is 
inoperable when SW1 is 
closed.

(1), (2)
No voltage 
a-contact

Yellow (2)

Red (3)

White (4)

Green (1)

Black (5)

2m

(locally procured)

Remote ON/OFF Adapter NRB-1HE

CN705

Control circuit board of the 
Air to Air Heat Exchanger

SW2

Low is applied when SW2 
is closed, and High when 
it is open.

As these terminals are not used, insulate them.

(1), (3)
No voltage 
a-contact

Yellow (2)

Red (3)

White (4)

Green (1)

Black (5)

2m

3) When switching between Bypass mode/Heat exchange ventilation from an external device 

SW3 [Bypass mode ventilation: ON, Heat exchanging ventilation: OFF]

• For NRC-01HE (remote controller for the Air to Air Heat Exchanger), the message on the display is 

changed.

• If a command is sent to one of the units in the group, all the Air to Air Heat Exchangers in the group operate 

together.

• The latter operation of the remote controller or the external device overrides the former.

NOTE

The operation mode will be automatically changed to Heat exchange mode when outdoor air temperature is below 15°C 
during Bypass mode. The display remains Bypass mode.

4

Connecting an auxiliary fan or monitoring operation output (External Output)

Connect to the terminal block for external output (1 and 2) in the electrical control box

Connection wire (locally procured): 2-core wire (H07 RN-F or 60245 IEC 66) 1.0mm

2

 to 2.5mm

2

 

Contact is on during normal operation as factory default.

• Contact is off during 24-hour ventilation mode, nighttime heat purge operation, delay mode or cold mode 

(temperature is below -10°C) as factory default.

• The operation output settings can be changed. Refer to "Setting for changing the operation output" on 

page 21.

Rated contact

Maximum: 240VAC, 1A
Minimum: 220VAC, 100mA

24VDC, 1A
5VDC, 100mA

(locally procured)

Remote ON/OFF Adapter NRB-1HE

CN705

Control circuit board of the 
Air to Air Heat Exchanger

SW3

Bypass mode is applied when SW3 
is closed, and Heat exchange 
ventilation when it is open.

As these terminals are not used, insulate them.

(1), (4)
No voltage 
a-contact

Yellow (2)

Red (3)

White (4)

Green (1)

Black (5)

2m

Power supply

Contact

Auxiliary 

fan

Terminal block for external output

Lamp or management device

Terminal block for external output

If external devices is used working at a higher voltage and current than the rated values, install a relay 
according to the diagram above.
Rated relay: 220-240VAC

To power

supply

Relay contact

External device

Contact

External device

External device

220-240V~, 50Hz
220V~, 60Hz

31-EN

32-EN

+00ET9X463301_01EN.book  Page 16  Thursday, January 20, 2011  4:41 PM

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Содержание VN-M1000HE

Страница 1: ...ocomputer control type Model name VN M150HE VN M250HE VN M350HE VN M500HE VN M650HE VN M800HE VN M1000HE Installation Manual xx Xxxxx Installation Manual For commercial use 00ET9X463301_01EN book Page 1 Thursday January 20 2011 4 41 PM AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 2: ...atively he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations The qualified installer who is allowed to do the electrical work involved in installation relocation and removal has the qualifications pertaining to this electrical work as stipulated by the local laws and r...

Страница 3: ...ove the electrical control cover or inspection cover of the Air to Air Heat Exchanger to undertake work Wear protective gloves and safety work clothing during installation servicing and removal When working at heights use a ladder which complies with the ISO 14122 standard and follow the procedure in the ladder s instructions Also wear a helmet for use in industry as protective gear to undertake t...

Страница 4: ...to Air Heat Exchanger falling do not approach the Air to Air Heat Exchanger but set the circuit breaker to the OFF position and contact a qualified service person 1 to have the repairs done Do not set the circuit breaker to the ON position until the repairs are completed Relocation Only a qualified installer 1 or qualified service person 1 is allowed to relocate the Air to Air Heat Exchanger It is...

Страница 5: ...ons or temperature humidity of the ceiling cavity even though the conditions for use are observed In this case add a heat insulator Do not install the unit in a place where there is something that must not become wet Depending on the temperature or humidity of outdoor air and the installation place water droplets may fall from the unit As shown in the figure to the below suppose a high temp absorb...

Страница 6: ...E 900 670 115 810 957 900 454 97 Ø145 Ø158 162 290 145 Ø150 VN M350HE 900 670 115 810 957 900 454 97 Ø145 Ø158 162 290 145 Ø150 VN M500HE 1140 800 170 1050 1197 1140 454 80 Ø195 Ø212 350 175 Ø200 VN M650HE 1140 800 170 1050 1197 1140 454 80 Ø195 Ø212 350 175 Ø200 VN M800HE 1189 800 195 1099 1246 1189 454 85 Ø245 Ø262 400 200 Ø250 VN M1000HE 1189 800 195 1099 1246 1189 454 85 Ø245 Ø262 400 200 Ø250...

Страница 7: ...t M10 or M12 Hanging bolt Nut Washer Hanging bracket Washer Nut Model name Weight kg Hanging bolt VN M150HE 36 M10 M12 VN M250HE 36 VN M350HE 38 VN M500HE 53 VN M650HE 53 VN M800HE 70 VN M1000HE 70 Hanging bolt Vibration proof fixture Vibration proof fixture Unit Duct Installation Duct installation is necessary to protect against access to live parts rain water or contact with moving parts Seal th...

Страница 8: ...fer from overheating or burnout Item Model name VN Power supply for Air to Air Heat Exchanger 1 Power supply Circuit breaker switch Power supply wire Current rating Fuse rating Air to Air Heat Exchanger M150HE to M1000HE 220V 240V 50Hz 220V 60Hz 15A 3 core 1 5 mm2 or 2 5 mm2 H07 RN F or 60245 IEC 66 1 Prepare the exclusive power supply for the Air to Air Heat Exchanger U3 U4 A B Communication wire...

Страница 9: ...for central control Wiring for the remote controller Wired remote controller sold separately Indoor control circuit board MCC1615 Connector White White Connector Black White Orange External output 220 240V under 1A each 5 External input sold separately No voltage a contact input Voltage DC 12V 24V input Operation output White White White Red Red White Red Blue Black Connector White 6 White Yellow ...

Страница 10: ...ire Earth line In a central control system connect the copper braid shield of central control wire 2 core shielded wire Switching between Extra High and High WARNING Turn off the circuit breaker before switching between Extra High and High When switching to Extra High connect the black lead wire Extra High to the connector The blue lead wire High is connected as factory default Connect the black l...

Страница 11: ...ventilation fan speed and ventilation mode of the Air to Air Heat Exchanger The remote controllers for the air conditioners RBC AMT32E cannot be used to control the group of the Air to Air Heat Exchangers Only on off operation is available for RBC AMS41E Central control system When controlling the air conditioner and the Air to Air Heat Exchanger separately The central controller can be used to ON...

Страница 12: ...rolling the air conditioner and Air to Air Heat Exchanger together No of Air to Air Heat Exchangers Multiple 1 Multiple 1 Multiple Operation together with the air conditioners No Yes Remote controller inter unit wiring Necessary Not necessary Necessary Central control wiring Necessary Header unit only Not necessary Circuit board of the Air to Air Heat Exchanger 1 Line system address Fixed The line...

Страница 13: ...for the Air to Air Heat Exchanger For details on how to install the remote controller for the Air to Air Heat Exchanger refer to the Installation Manual accessory with the remote controller One or multiple Air to Air Heat Exchanger s can be controlled by using two remote controllers Up to two remote controllers can be installed How to install To use two remote controllers follow the procedure belo...

Страница 14: ...ng between indoor units Indoor unit Outdoor unit Power supply Remote controller inter unit wiring Remote controller follower Remote controller header Indoor unit Air to Air Heat Exchanger Power supply Power supply Power supply Power supply Air to Air Heat Exchanger Central control system When controlling the Air to Air Heat Exchanger only Changing the group address No 4 of SW703 Settings for chang...

Страница 15: ...nger Power supply Central controller Outdoor unit Control wiring between indoor and outdoor units Control wiring between indoor units Central control wiring Remote controller inter unit wiring Remote controller inter unit wiring Central control wiring Central control system When controlling the air conditioner and Air to Air Heat Exchanger together Changing the group address No 4 of SW703 The sett...

Страница 16: ...rd of the Air to Air Heat Exchanger Remote ON OFF Adapter NRB 1HE locally procured 1 2 DC12V DC24V non polarity CN706 Blue 1 Orange 2 2m 2 When the output signal of the external device is a no voltage a contact static signal Transmission wire used to extend must be locally procured Non polarity shielded wire H05 VVC4V5 K or 60227 IEC 74 0 5mm2 Maximum length 50m Insert the Remote ON OFF Adapter NR...

Страница 17: ...reen 1 Black 5 2m 3 When switching between Bypass mode Heat exchange ventilation from an external device SW3 Bypass mode ventilation ON Heat exchanging ventilation OFF For NRC 01HE remote controller for the Air to Air Heat Exchanger the message on the display is changed If a command is sent to one of the units in the group all the Air to Air Heat Exchangers in the group operate together The latter...

Страница 18: ... For details on the auto address setting of air conditioners when operating together with a SMMS series air conditioner adjust the auto address setting on the circuit board of the outdoor interface refer to the Installation Manual of the SMMS series air conditioner For details on the auto address setting of air conditioners when operating together with a DI SDI series air conditioner the action is...

Страница 19: ...is setting is necessary for all the Air to Air Heat Exchangers in the group 4B Delayed operation 0000 Invalid 0001 0006 Setting valve x 10 minutes delay Delaying the Air to Air Heat Exchanger operation to reduce the air conditioning load when starting running the air conditioner 0000 Invalid Adjusting this setting is necessary for all the Air to Air Heat Exchangers in the group System equipped wit...

Страница 20: ...DATA and description Factory default Note Setting of the Air to Air Heat Exchanger single operation Setting for the header air conditioner Single operation of the Air to Air Heat Exchanger is possible when operation of the Air to Air Heat Exchanger is linked with that of the air conditioners Use the button of the wired remote controller While the Air to Air Heat Exchanger is in operation is displa...

Страница 21: ... Air Heat Exchanger to which the Remote ON OFF Adapter NRB 1HE sold separately is connected Select 4E in step 3 on page 17 Select a value from the table on the below in step 4 on page 17 Ventilation mode setting The setting of the ventilation mode can be changed when the remote controller for air conditioners RBC AMT32E RBC AMS41E or a system without a remote controller is used Adjusting this sett...

Страница 22: ...ion or nighttime heat purge operation Contact is on when 24 hour ventilation is stopped intermittently Contact is off during normal operation or when the nighttime heat purge operation is on standby paused before the monitoring operation of the nighttime heat purge operation starts Contact is off during cold mode while the temperature is below 10 C 0003 Contact is on only when SA fan is running Co...

Страница 23: ... amount is reduced and ventilation effect will be deteriorated Clean the filter and heat exchange element regularly according to the extent of dust accumulation WARNING Before performing maintenance stop the unit then turn off the breaker Otherwise an electric shock or injury may result Do not pour or spray water or detergent on the electric parts Otherwise an electrical leakage may occur and a fi...

Страница 24: ...eaner with a brush and stroke the brush gently on the heat exchange element Do not press the nozzle of the vacuum cleaner hard against the heat exchange element otherwise the surface of it will be scratched Do not wash the heat exchange element in water Contact the dealer or installer when the heat exchange element is damaged and replacing it is necessary Reinstallation after maintenance 1 Attach ...

Страница 25: ...rs Remote controller communication error No signal can be received from the indoor unit E02 Remote controller transmission error Remote controller System interconnecting wires indoor P C board remote controller No signal can be sent to the indoor unit E03 Indoor unit remote controller regular communication error Indoor Remote controller network adapter indoor P C board No data is received from the...

Страница 26: ...Toshiba XXXXXXX X X ET9X463301 00ET9X463301_01EN book Page 24 Thursday January 20 2011 4 41 PM AMP Air Conditioning www ampair co uk sales ampair co uk ...

Отзывы: