164
Ethernet module User’s Manual
Chapter 7 RAS Information
7
7.2 Down Information
When an EN311 goes down, the factor that caused that transition is stored in the S
controller interface memory as one word of data. This data can be read by the S
controller with the MREAD instruction.
Table 7-1 lists the down information error codes and the factors that caused the transition
to down mode.
Important note
This area is a read-only area. Do not attempt to write data to it using the MWRITE
instruction. If you do, data may no longer be read correctly.
Table 7-1 Down Information
Error code (H)
Description
0010
Watchdog timeout
0020
Memory bus stall
0030
A TRAP occurred
0040
Jabbering timeout
0050
LAN controller check error
0160
ROM BCC check data match error
0260
System RAM area check error
0360
S controller interface memory check error
0500, 0501
Semaphore acquisition error
0502, 0503
Semaphore acquisition error
0504
MBX receive error
0505
MBX send error
0506
TCP resend queue full
0507
Acquired buffer in use
0508
Error in acquiring initial buffer
Содержание V Series
Страница 1: ...6F8C0904 Integrated Controller V Series Ethernet module EN311 User s Manual Sep 30 2004 ...
Страница 12: ......
Страница 16: ......
Страница 34: ......
Страница 40: ......
Страница 106: ......
Страница 180: ......
Страница 199: ...6F8C0904 179 7 5 RAS Information Readout 7 Figure 7 1 Packet Format IP Datagram ...
Страница 200: ...180 Ethernet module User s Manual Chapter 7 RAS Information 7 ...
Страница 224: ......
Страница 240: ......
Страница 244: ......
Страница 248: ......
Страница 250: ......
Страница 256: ......
Страница 258: ......