6F8C0904
171
7.5 RAS Information Readout
7
(3) Important notes
• This request can be used in run and standby modes.
• The read out RAS information is stored in the specified register area as shown below.
• A boundary error occurs if it is not possible to allocate an area that is the size of the
read out RAS information plus one word for the RAS information storage area.
Error status : -5060(16#EC3C)
• A parameter error occurs on any of the following transfer parameter settings.
Error status : -5001(16#EC77)
If the RAS request type is out of range (a value other than 1 to 5).
If the start position is out of range (a value of 4 or larger) for MIB information.
If the start position is out of range (a value of 161 or larger) for event trace information.
If the read count is out of range (a value of 31 or larger) for event trace information.
(4) Sample program
(a) Defining the variables
VAR
RAS_REQ1:
BOOL;
RAS_COMPLETE1:
BOOL;
RAS_ERROR1:
BOOL;
RCV_STATUS1:
INT; (* RAS information readout request error status *)
URCV_T_11:
URCV_T;
END_VAR
RAS information word count
←
Specified register start address
RAS information
←
A register area whose size is the size of the read
out RAS information plus one word must be
allocated.
Содержание V Series
Страница 1: ...6F8C0904 Integrated Controller V Series Ethernet module EN311 User s Manual Sep 30 2004 ...
Страница 12: ......
Страница 16: ......
Страница 34: ......
Страница 40: ......
Страница 106: ......
Страница 180: ......
Страница 199: ...6F8C0904 179 7 5 RAS Information Readout 7 Figure 7 1 Packet Format IP Datagram ...
Страница 200: ...180 Ethernet module User s Manual Chapter 7 RAS Information 7 ...
Страница 224: ......
Страница 240: ......
Страница 244: ......
Страница 248: ......
Страница 250: ......
Страница 256: ......
Страница 258: ......