F-7
6.3 Selection of terminal functions
6.3.1 Keeping an input terminal function always active (ON)
:
Always active function selection
■
Parameter setting
Title
Function
Adjustment range
Default setting
Always active function selection
〜
※
The selected function is kept always active regardless of the type of logic (positive or negative) in the
table of function settings in 7.2.1.
6.3.2 Changing input terminal functions
:
Input terminal selection #1 (F)
:
Input terminal selection #6 (S2)
:
Input terminal selection #2 (R)
:
Input terminal selection #7 (S3)
:
Input terminal selection #3 (ST)
:
Input terminal selection #8 (S4)
:
Input terminal selection #4 (RES)
〜
:
Input terminal selection #9
〜
#16
:
Input terminal selection #5 (S1)
Refer to 7.2.1 for details.
6.3.3 Signal on completion of acceleration/deceleration (OUT 2)
:
Output terminal selection #2 (OUT2)
■
Setting of output terminal
Title
Function
Adjustment range
Setting value
Output terminal
selection #2 (OUT2)
〜
: Acceleration/deceleration
completion(a-contact)
or
: Acceleration/deceleration
completion
(
b-contact)
Note)
OUT1 for putting out a signal, select the parameter
.
・
Function
This parameter is used to select a function to be kept always active (ON) from among the
input terminal functions. (One function can be selected)
・
Function
If this parameter is so set, a signal is put out on completion of acceleration/deceleration.
★
Open collector output terminal OUT1 or OUT2 (24 Vdc - max. 50 mA)
Output frequency [Hz]
[s]
ON
OFF
Acc. Completed(a-contact)
Acc. Completed(b-contact)
ON
OFF
0
Reference
(Speed reach detection band)
(
)