background image

   

E6581440 

 

- 6 - 

 

SW

ID 

1 2 3 4 5 6 7

8

 SW

ID 

1

2

3 4 5 6 7

8

64 

OFF  ON  OFF OFF OFF OFF OFF OFF

 

96 

OFF ON ON  OFF OFF OFF OFF OFF

65 

OFF  ON  OFF OFF OFF OFF OFF ON

 

97 

OFF ON ON  OFF OFF OFF OFF ON

66 

OFF ON OFF OFF OFF OFF ON OFF

 

98 

OFF ON ON OFF OFF OFF ON OFF

67 

OFF ON OFF OFF OFF OFF ON ON

 

99 

OFF ON ON OFF OFF OFF ON ON

68 

OFF ON OFF OFF OFF ON OFF OFF

 

100  OFF ON ON OFF OFF ON OFF OFF

69 

OFF ON OFF OFF OFF ON OFF ON

 

101  OFF ON ON OFF OFF ON OFF ON

70 

OFF ON OFF OFF OFF ON  ON OFF

 

102  OFF ON ON OFF OFF ON ON OFF

71 

OFF ON OFF OFF OFF ON  ON ON

 

103  OFF ON ON OFF OFF ON ON ON

72 

OFF ON OFF OFF ON OFF OFF OFF

 

104  OFF ON ON OFF ON OFF OFF OFF

73 

OFF ON OFF OFF ON OFF OFF ON

 

105  OFF ON ON OFF ON OFF OFF ON

74 

OFF ON OFF OFF ON OFF ON OFF

 

106  OFF ON ON OFF ON OFF ON OFF

75 

OFF ON OFF OFF ON OFF ON ON

 

107  OFF ON ON OFF ON OFF ON ON

76 

OFF ON OFF OFF ON  ON OFF OFF

 

108  OFF ON ON OFF ON  ON OFF OFF

77 

OFF ON OFF OFF ON  ON OFF ON

 

109  OFF ON ON OFF ON  ON OFF ON

78 

OFF ON OFF OFF ON  ON  ON OFF

 

110  OFF ON ON OFF ON  ON ON OFF

79 

OFF ON OFF OFF ON  ON  ON ON

 

111  OFF ON ON OFF ON  ON ON ON

80 

OFF ON OFF ON OFF OFF OFF OFF

 

112  OFF ON ON  ON OFF OFF OFF OFF

81 

OFF ON OFF ON OFF OFF OFF ON

 

113  OFF ON ON  ON OFF OFF OFF ON

82 

OFF ON OFF ON OFF OFF ON OFF

 

114  OFF ON ON  ON OFF OFF ON OFF

83 

OFF ON OFF ON OFF OFF ON ON

 

115  OFF ON ON  ON OFF OFF ON ON

84 

OFF ON OFF ON OFF ON OFF OFF

 

116  OFF ON ON  ON OFF ON OFF OFF

85 

OFF ON OFF ON OFF ON OFF ON

 

117  OFF ON ON  ON OFF ON OFF ON

86 

OFF ON OFF ON OFF ON  ON OFF

 

118  OFF ON ON  ON OFF ON ON OFF

87 

OFF ON OFF ON OFF ON  ON ON

 

119  OFF ON ON  ON OFF ON ON ON

88 

OFF ON OFF ON  ON OFF OFF OFF

 

120  OFF ON ON  ON  ON OFF OFF OFF

89 

OFF ON OFF ON  ON OFF OFF ON

 

121  OFF ON ON  ON  ON OFF OFF ON

90 

OFF ON OFF ON  ON OFF ON OFF

 

122  OFF ON ON  ON  ON OFF ON OFF

91 

OFF ON OFF ON  ON OFF ON ON

 

123  OFF ON ON  ON  ON OFF ON ON

92 

OFF ON OFF ON ON ON OFF OFF

 

124  OFF ON ON ON ON ON OFF OFF

93 

OFF ON OFF ON ON ON OFF ON

 

125  OFF ON ON ON ON ON OFF ON

94 

OFF ON OFF ON ON ON ON OFF

 

126  OFF ON ON ON ON ON ON OFF

95 

OFF ON OFF ON ON ON ON ON

 

127  OFF ON ON ON ON ON ON ON

 
 

 

Содержание TOSVERT BCN001Z

Страница 1: ...uction manual is delivered to the end user of BACnet Option unit 2 Read this manual before installing or operating the BACnet Option unit Keep it in a safe place for reference 3 All information contained in this manual are subject to change without notice Please confirm the latest information on our web site ...

Страница 2: ... valid range to network variables Otherwise the motor may suddenly start stop and that may result in injuries Mandatory Use an additional safety device with your system to prevent a serious accident due to the network malfunctions Usage without an additional safety device may cause an accident Caution Mandatory Set up Communication error trip function see below to stop the Inverter when the option...

Страница 3: ...ter f835 8 3 6 MaxInfoframe f836 8 3 7 MAC address monitor f853 8 3 8 Number of motor poles for communication f856 8 4 FUNCTIONS 9 4 1 Object Property support Matrix 9 4 2 Drive I O Objects 10 4 2 1 Binary Input Object Instance 10 4 2 2 Binary Output Object Instance 11 4 2 3 Binary Value Objects Instance 12 4 2 4 Analog Input Object Instance 13 4 2 5 Analog Output Object Instance 13 4 2 6 Analog V...

Страница 4: ...nal symbol Function Electrical specifications Internal circuits B Communication signal A Communication signal GND Signal common SCR BACnet communication signal EIA 485 Shield terminal B A GND SCR 47k 47k 4 7k 4 7k 120 SW102 TERM Don t use this connecter Connector to the inverter MS TP MAC address switches See 2 4 Don t use this switch BACnet Connector See 2 2 Terminal connector MSTB 2 5 4 STF 5 08...

Страница 5: ...0 5s Invalid configuration was detected MAC address max master Note When inverter occurred in E 23 or E 24 the LED becomes this state D COM LED 3 times in 2 seconds OFF for 1 second ERR LED OFF Waiting for Auto baudrate detection E COM LED Flashing ERR LED OFF Valid message was received for this node F COM LED OFF ERR LED Flashing Invalid message was received any node G COM LED OFF ERR LED OFF No ...

Страница 6: ...ON ON 12 OFF OFF OFF OFF ON ON OFF OFF 44 OFF OFF ON OFF ON ON OFF OFF 13 OFF OFF OFF OFF ON ON OFF ON 45 OFF OFF ON OFF ON ON OFF ON 14 OFF OFF OFF OFF ON ON ON OFF 46 OFF OFF ON OFF ON ON ON OFF 15 OFF OFF OFF OFF ON ON ON ON 47 OFF OFF ON OFF ON ON ON ON 16 OFF OFF OFF ON OFF OFF OFF OFF 48 OFF OFF ON ON OFF OFF OFF OFF 17 OFF OFF OFF ON OFF OFF OFF ON 49 OFF OFF ON ON OFF OFF OFF ON 18 OFF OFF...

Страница 7: ... ON OFF ON ON OFF ON 78 OFF ON OFF OFF ON ON ON OFF 110 OFF ON ON OFF ON ON ON OFF 79 OFF ON OFF OFF ON ON ON ON 111 OFF ON ON OFF ON ON ON ON 80 OFF ON OFF ON OFF OFF OFF OFF 112 OFF ON ON ON OFF OFF OFF OFF 81 OFF ON OFF ON OFF OFF OFF ON 113 OFF ON ON ON OFF OFF OFF ON 82 OFF ON OFF ON OFF OFF ON OFF 114 OFF ON ON ON OFF OFF ON OFF 83 OFF ON OFF ON OFF OFF ON ON 115 OFF ON ON ON OFF OFF ON ON 8...

Страница 8: ...ire breaks 0 Inverter stop communication command frequency mode open by cmod fmod 1 None continued operation 2 Deceleration stop 3 Coast stop 4 Network error err8 trip 5 Preset speed operation by f852 setting 0 f852 Preset speed operation selection 0 None 1 15 Preset speed operation by parameter setting 0 f853 MAC address 2 Read Only BCN001Z MS TP MAC address monitor Set DIP switches on the board ...

Страница 9: ...e in the network The instance number is 22bit data length and set the number of the option board as below Instance number f833 x 1000 f834 f834 1000 Instance number 4194304 3 5 MaxMaster f835 Set the maximum master number of the segment The BACnet option unit polls master station node from 0 to MaxMaster so set MaxMaster to be small number to be a fast response time 3 6 MaxInfoframe f836 Set the m...

Страница 10: ...ct Type System Status Vendor Name Vendor Identifier Model Name Firmware Revision Appl Software Revision Protocol Version Protocol Revision Services Supported Object Types Supported Object List Max APDU Length Segmentation Support APDU Timeout Number APDU Retries Max Master Max Info Frames Device Address Binding Database Revision Present Value Status Flags Event State Out of Service Units Priority ...

Страница 11: ...N OFF R Binary input 4 RO 5 ACT Inverter OUT5 terminal monitor f136 ON OFF R Binary input 5 RO 6 ACT Inverter OUT6 terminal monitor f137 ON OFF R Binary input 6 DI 1 ACT Inverter F terminal monitor ON OFF R Binary input 7 DI 2 ACT Inverter R terminal monitor ON OFF R Binary input 9 DI 4 ACT Inverter RES terminal monitor ON OFF R Binary input 10 DI 5 ACT Inverter S1 terminal monitor ON OFF R Binary...

Страница 12: ...ription Active Inactive Access Binary Output 0 RO 1 CMD FL terminal control f132 92 ON OFF C Binary Output 1 RO 2 CMD OUT1 terminal control f130 94 ON OFF C Binary Output 2 RO 3 CMD OUT2 terminal control f131 96 ON OFF C Binary Output 3 RO 4 CMD R2 terminal control f138 98 ON OFF C Binary Output 4 RO 5 CMD OUT3 terminal control f136 100 ON OFF C Binary Output 5 RO 6 CMD OUT4 terminal control f137 ...

Страница 13: ... object access to parameter fc91 bit10 YES NO R 7 DRIVE READY The VSD is ready and waits a start command This object access to parameter fd01 bit14 READY NOT READY R 8 AT SETPOINT The VSD has reached the target speed REACHED NO R 10 RUN STOP CMD Commands a drive start START STOP C 11 FWD REV CMD Commands a motor direction s change REV FWD C 14 FAULT RESET Command to reset faults RESET NO C 15 MBOX...

Страница 14: ...ETB004Z Expansion IO card option R Read only W Writable C Commandable 4 2 5 Analog Output Object Instance The analog output objects allow to control inverter analog AM FM output levels and also can be used priority array and relinquish default property These objects only write to inverter parameters fa51 fa54 It is necessary to set meter function selection parameters see below table to 31 Instance...

Страница 15: ...from fe30 100 3 VSD rate voltage Motor rate current R 7 DRIVE TEMP Drive Thermal State fd24 OL1 will be caused if this value reaches 100 R 8 KWH R Energy counter Calculate from fd76 fd77 KWH R 10 PRC PID FBCK PID regulator feedback fe22 vl 100 00 R 14 RUN TIME Cumulate operation time fe14 hour R 16 INPUT REF 1 Speed reference fa07 vl 100 C 18 LAST FLT Current fault code fc90 R 19 PREV FLT 1 Past f...

Страница 16: ...bject Name VF PS1 Object Type 8 device Vendor Name TOSHIBA Vendor Identifier 203 Model Name VFPS1 2007P depend on the VSD model Firmware Revision V1 00 depend on the option software version Application Software Version V6 20 depend on the VSD software version Protocol Version 1 Protocol Revision 2 ...

Страница 17: ...d communication number is illegal MBOX READ value remains 1 It allow to check read failure Binary value 16 MBOX WRITE Write Command If MBOX WRITE command value is set to 1 the inverter parameter specified by MBOX PARAM is written the data specified by MBOX DATA and MBOX WRITE set to 0 automatically If parameter writing is denied or specified communication number is illegal MBOX WRITE value remains...

Страница 18: ...array fault err6 26 1A Output current detector error err7 27 1B Option error err8 29 1D Low current operation status uc 30 1E Undervoltage main circuit up1 32 20 Over torque trip ot 33 21 Ground fault trip ef1 34 22 Ground fault trip ef2 36 24 Dynamic braking abnormal element ocr 37 25 Overcurrent during acceleration element overheat oc1p 38 26 Overcurrent during deceleration element overheat oc2p...

Страница 19: ...VDC supplied from the inverter Network specification Item Specification Data link physical layer Master Slave Token Passing MS TP Node type Master node Maximum connection units Maximum 32 units within one segment Communication baudrate 9600 19200 38400 76800bps Auto adaptive is supported Bias resistor and termination Local bias resistors are mounted Termination resistor 120 ohm can be select by SW...

Отзывы: