background image

– 6 –

EN

Connecting the drain hose to the 

indoor unit side

1

Insert the drain hose provided with the indoor 

unit into the drain pipe connection aperture of the 

indoor unit drain pan and the drain pipe 

connection aperture of the drain pump kit drain 

pan. 

When doing this, insert the drain hose until end 

of the drain pipe connection port.

2

Securely tighten the 2 hose band provided with 

the indoor unit so they are from 10 to 15 mm from 

the end of the pipe connection port.

3

Cut the heat insulator for the drain hose provided 

with the indoor unit (from 190 × 190 to 160 × 190), 

and then wrap it around the connection of the drain 

pan and the drain hose so there are no gaps, then 

use 2 banding band provided with the indoor unit to 

tighten the heat insulator so it does not come open.

* Do not tighten the banding band so much that the 

insulation is compressed.

Drain hose connection on the 

drain pump kit

* Depending on how the water drains, you may work on the 

indoor unit as it hangs.

1

Insert the drain hose provided with the indoor 

unit into the drain pipe connection port on the top 

of the drain pump kit.

2

Securely tighten the hose band provided with the 

drain pump kit at the edge near the end of the 

drain hose. 

Turn the hose band so they are easy to tighten 

and then use a flathead screwdriver to tighten 

them.

3

Wrap the heat insulation for the drain connection 

provided with the drain pump kit so it completely 

covers the drain hose and butts against the top 

plate of the drain pump kit.

4

Insert the locally procured hard vinyl chloride 

pipe (VP25) into the drain hose, tighten a hose 

band around the edge near the end of the drain 

hose, and wrap the heat insulation for the drain 

connection so the hose band are completely 

covered and hidden.

5

Wrap the heat insulated piping provided with the 

drain pump kit so it butts against the top plate of 

the drain pump kit so everything is covered.

* If the installation is less than 150 mm from the top of the 

indoor unit, do not use an elbow, bend the drain hose 

provided and connect to it directly (the radius of the bend 

should be as large as possible).

Indoor unit drain 

pan

Drain hose 

(Provided with 

indoor unit)

Confirm that 

soft hose is 

pushed in up 

to the end of 

the drain pan.

Drain pump kit drain 

pan

10 ~ 15 mm

10 ~ 15 mm

Fit the attached hose band to the end of the hose, with both of 

the two knobs oriented sideways.

Wrap to cover the connection of the drain 

hose and drain pan.

Drain hose 

(Provided with indoor unit)

Banding band

(Provided with indoor unit)

Hose band

(Provided with indoor unit)

Heat insulator (provided with indoor unit) 

(cut to 160 × 190)

Lap the 

attached heat 

insulation so 

that the one end 

is put on the 

other end at the 

upper side.

Drain hose

Hose band (provided with drain pump kit)

* Tighten at the edge near the end of the 

drain hose.

Hose band

Heat insulation for drain connection

(provided with drain pump kit)

* Wrap with no gaps and butted 

against the top plate of the drain 

pump kit.

Top plate of drain pump kit

Drain hose

(provided with

drain pump kit)

Heat insulated pipe (provided with 

drain pump kit)

* Wrap the insulated piping with 

no gaps and butted against the 

sheet metal of the top of the 

drain pump kit.

Hard vinyl chloride 

pipe VP25

(Locally procured)

6

00 mm or less ab

ove th

top of the indoor

 unit

300 mm

Heat insulation for drain 

connection 

(provided with drain pump kit)

* Wrap so the hose clamp is 

hidden.

Hose band (provided with 

drain pump kit)

* Tighten at the edge 

near the end of the 

drain hose.

Drain hose (provided with 

drain pump kit)

Hose band 

(provided with drain pump kit)

+00EH99545701_00Ta.book  Page 6  Wednesday, June 5, 2013  2:38 PM

Содержание TCB-DP31CE

Страница 1: ...ation 11 Installationshandbuch 21 Manuale d installazione 31 Manual de instalación 41 Manual de Instalação 51 Installatiehandleiding 61 Εγχειρίδιο εγκατάστασης 71 安装说明书 81 AIR CONDITIONER SPLIT TYPE Drain pump kit Model name TCB DP31CE Installation Manual 00EH99545701_00Ta book Page 1 Wednesday June 5 2013 2 38 PM ...

Страница 2: ...Qty Shape Application Drain pump 1 Bracket 1 For mounting the drain pump kit Drain hose 1 For connecting to the vinyl chloride pipe of the drain pump kit Heat insulating pipe 1 For insulating the drain hose Hose band 2 For clamping the drain hose Heat insulator 2 For insulating the drain hose connection Screws 4 For installing the drain pump kit For fastening the drain pump kit bracket Installatio...

Страница 3: ... is not strong enough the unit may fall and result in injury Do the installation to specifications that can withstand earthquakes or strong winds such as in a typhoon A defective installation could result in an accident if the air conditioner tips over or falls Ventilate the area if the refrigerant gas leaks during installation work If the refrigerant gas is exposed to fire it produces poison gas ...

Страница 4: ... the installation is being done units mm Position of knockout on the top of the indoor unit Position of ceiling opening hole Position of refrigerant pipes and drain pipe 66 109 40 145 450 450 200 320 90 150 170 23 110 120 Ceiling opening hole Ø100 2 holes Access panel 23 90 152 300 154 103 98 40 170 Drain pipe Refrigerant pipe liquid side Elbow piping kit Refrigerant pipe gas side Elbow piping kit...

Страница 5: ...panel fixing screws 1 each at right and left slide the side panel forward and then remove it Knock out hole Open the hole for directing refrigerant pipes and drain pipe upward knockout hole Connecting the elbow piping kit Connect the elbow piping kit sold separately to the indoor unit Always use two wrenches to connect pipes to the indoor unit Refer to the following table for the tightening torque...

Страница 6: ...iping is exposed Exposed pipes may cause water leaks Installing the drain pump kit 1 Attach the drain pump kit bracket to the inside of the rear panel of the indoor unit 1 screw 2 Hook the temporary hook of the drain pump kit from the inside out through the slit in the side of the indoor unit Screw the drain pump kit onto the indoor unit 3 screws Top panel side panel and drain pump kit bracket See...

Страница 7: ...hose band are completely covered and hidden 5 Wrap the heat insulated piping provided with the drain pump kit so it butts against the top plate of the drain pump kit so everything is covered If the installation is less than 150 mm from the top of the indoor unit do not use an elbow bend the drain hose provided and connect to it directly the radius of the bend should be as large as possible Indoor ...

Страница 8: ...e following figure Do not provide any air vents Otherwise the drain water will spout causing water to leak Do not allow any force to be applied to the connection area with the drain pipe A hard vinyl chloride pipe cannot be connected to the drain pipe connecting port of the drain pump kit Be absolutely sure to use the drain hose provided for the connections with the drain pipe connecting port Adhe...

Страница 9: ... control box to a position where it is easy to work 2 Connect the connector 2P white for the drain pump in the drain pump kit to CN504 2P white on the indoor unit P C board and connect float switch connector 3P red to CN34 3P red on the indoor unit P C board Remove the short plug CN34 3P red to do this 3 Be careful to not pinch any wires during reassembly 60 50 Cut a Ø70 hole Heat insulating for d...

Страница 10: ...bacterial glass holder has a hook lift the cover up as you remove it Refer to Fig 1 and Fig 2 3 Remove the antibacterial glass holder that is hanging inside the drain pump kit through the hole that is in the top Refer to Fig 3 4 Insert the new antibacterial glass holder and securely close the cover of the antibacterial glass holder and fasten it in place The top of the cover of the antibacterial g...

Страница 11: ...bacterial glass holder as explained in 6 Regarding antibacterial glass After checking refer to 6 Regarding antibacterial glass and be sure to fasten the cover of the antibacterial glass holder with the screw Maintenance This product has an internal drain pump The pump needs to be cleaned periodically because the water is prevented from draining if the pump clogs due to being operated in a dusty or...

Страница 12: ...Toshiba XXXXXXX X X EH99545701 00EH99545701_00Ta book Page 91 Wednesday June 5 2013 2 38 PM ...

Отзывы: