background image

– 9 –

6

Regarding antibacterial glass

This product has internal antibacterial glass. Antibacterial glass is a consumable part. It should be replaced after about 10,000 

hours of regular air conditioner operation. (If the air conditioner is operated 10 hours every day for five months, that is 1,500 

hours for the year.) Use the antibacterial glass holder (service part No. : 43479037) when you replace it.

Replacing antibacterial glass

1

Remove the screw holding the cover of the antibacterial glass holder.

2

The cover of the antibacterial glass holder has a hook, lift the cover up as you remove it. 

(Refer to Fig.1 and Fig.2)

3

Remove the antibacterial glass holder that is hanging inside the drain pump kit through the hole that is in 

the top. 

(Refer to Fig.3)

4

Insert the new antibacterial glass holder and securely close the cover of the antibacterial glass holder and 

fasten it in place. 

(The top of the cover of the antibacterial glass holder is a hook that hooks to the drain pump kit. Make sure 

that it is secure.)

Fig.1

Fig.2

Fig.3

Cover of the antibacterial glass holder

Remove this screw and then remove the cover 

of the antibacterial glass holder

2

1

Hook

Antibacterial glass holder

+00EH99545701_00Ta.book  Page 9  Wednesday, June 5, 2013  2:38 PM

Содержание TCB-DP31CE

Страница 1: ...ation 11 Installationshandbuch 21 Manuale d installazione 31 Manual de instalación 41 Manual de Instalação 51 Installatiehandleiding 61 Εγχειρίδιο εγκατάστασης 71 安装说明书 81 AIR CONDITIONER SPLIT TYPE Drain pump kit Model name TCB DP31CE Installation Manual 00EH99545701_00Ta book Page 1 Wednesday June 5 2013 2 38 PM ...

Страница 2: ...Qty Shape Application Drain pump 1 Bracket 1 For mounting the drain pump kit Drain hose 1 For connecting to the vinyl chloride pipe of the drain pump kit Heat insulating pipe 1 For insulating the drain hose Hose band 2 For clamping the drain hose Heat insulator 2 For insulating the drain hose connection Screws 4 For installing the drain pump kit For fastening the drain pump kit bracket Installatio...

Страница 3: ... is not strong enough the unit may fall and result in injury Do the installation to specifications that can withstand earthquakes or strong winds such as in a typhoon A defective installation could result in an accident if the air conditioner tips over or falls Ventilate the area if the refrigerant gas leaks during installation work If the refrigerant gas is exposed to fire it produces poison gas ...

Страница 4: ... the installation is being done units mm Position of knockout on the top of the indoor unit Position of ceiling opening hole Position of refrigerant pipes and drain pipe 66 109 40 145 450 450 200 320 90 150 170 23 110 120 Ceiling opening hole Ø100 2 holes Access panel 23 90 152 300 154 103 98 40 170 Drain pipe Refrigerant pipe liquid side Elbow piping kit Refrigerant pipe gas side Elbow piping kit...

Страница 5: ...panel fixing screws 1 each at right and left slide the side panel forward and then remove it Knock out hole Open the hole for directing refrigerant pipes and drain pipe upward knockout hole Connecting the elbow piping kit Connect the elbow piping kit sold separately to the indoor unit Always use two wrenches to connect pipes to the indoor unit Refer to the following table for the tightening torque...

Страница 6: ...iping is exposed Exposed pipes may cause water leaks Installing the drain pump kit 1 Attach the drain pump kit bracket to the inside of the rear panel of the indoor unit 1 screw 2 Hook the temporary hook of the drain pump kit from the inside out through the slit in the side of the indoor unit Screw the drain pump kit onto the indoor unit 3 screws Top panel side panel and drain pump kit bracket See...

Страница 7: ...hose band are completely covered and hidden 5 Wrap the heat insulated piping provided with the drain pump kit so it butts against the top plate of the drain pump kit so everything is covered If the installation is less than 150 mm from the top of the indoor unit do not use an elbow bend the drain hose provided and connect to it directly the radius of the bend should be as large as possible Indoor ...

Страница 8: ...e following figure Do not provide any air vents Otherwise the drain water will spout causing water to leak Do not allow any force to be applied to the connection area with the drain pipe A hard vinyl chloride pipe cannot be connected to the drain pipe connecting port of the drain pump kit Be absolutely sure to use the drain hose provided for the connections with the drain pipe connecting port Adhe...

Страница 9: ... control box to a position where it is easy to work 2 Connect the connector 2P white for the drain pump in the drain pump kit to CN504 2P white on the indoor unit P C board and connect float switch connector 3P red to CN34 3P red on the indoor unit P C board Remove the short plug CN34 3P red to do this 3 Be careful to not pinch any wires during reassembly 60 50 Cut a Ø70 hole Heat insulating for d...

Страница 10: ...bacterial glass holder has a hook lift the cover up as you remove it Refer to Fig 1 and Fig 2 3 Remove the antibacterial glass holder that is hanging inside the drain pump kit through the hole that is in the top Refer to Fig 3 4 Insert the new antibacterial glass holder and securely close the cover of the antibacterial glass holder and fasten it in place The top of the cover of the antibacterial g...

Страница 11: ...bacterial glass holder as explained in 6 Regarding antibacterial glass After checking refer to 6 Regarding antibacterial glass and be sure to fasten the cover of the antibacterial glass holder with the screw Maintenance This product has an internal drain pump The pump needs to be cleaned periodically because the water is prevented from draining if the pump clogs due to being operated in a dusty or...

Страница 12: ...Toshiba XXXXXXX X X EH99545701 00EH99545701_00Ta book Page 91 Wednesday June 5 2013 2 38 PM ...

Отзывы: