Settings of External Device
Set PC No. of the External Device using DIP Switches and the rotary switch of External Device.
Please refer to the manual of the External Device for more details.
After setting, reboot the External Device to enable the setting.
Setup Items
•
DIP Switch
•
Rotary switch
DIP Switch
Settings
*1
*1
For SW3 to SW6, if two or more than two switches are turned on, there will be a set error.
SW3 must be turned ON when connect to Display.
Setup Description
SW1
OFF
Set PC No. by combining with the rotary switch.
SW2
OFF
SW3
ON
Link Master
SW4
OFF
Link Slave
SW5
OFF
Remote Master
SW6
OFF
Remote Slave
Settings
Setup Description
0
PC No.
• Set PC No. using DIP Switches 1 and 2 and the rotary switch. Combination of possible
settings is as follows.
DIP Switch
PC No. that can be set
with the rotary switch
SW1
SW2
OFF
OFF
0 - 15
OFF
ON
16 - 31
ON
OFF
32 - 47
ON
ON
48 - 63