– 12 –
RAS-13SKH-ES/RAS-13SAH-ES
Heat exchanger
Indoor unit
Cross flow fan
Gas container connection (Reinstall etc.)
Heating
4-way valve
Heating Cooling
Compressor
Condenser
Propeller fan
Outdoor unit
Capillary tube
ø1,5x500
Cooling
Cooling
Mark ( ) means check points of Gas Leak
O.D.:9,52mm
O.D.:6,35mm
Cooling
Heating
Packed valve
(ø9,52)
Packed valve
(ø6,35)
0,49m
(Connecting pipe)
ø9,52
0,39m
(Connecting pipe)
ø6,35
(Note)
Maximum pipe length is 15m
Maximum pipe head is 6m
T1
P
Capillary tube
ø1,2x1200
Heating
Refrigerant
R-410A 0,80kg
PA160X2T-4FM
Muffler
Dryer
Standard pressure
Surface temp. of heat
P
exchanger interchanging
Fan speed
50Hz
(MPaG)
pipe T1 (°C)
(indoor)
RAS-13SKH-ES
RAS-13SKH-ES
Standard
2,7
43,0
High
Heating
High temperature*1
3,2 ~ 3,6
52,0 ~ 57,0
Low
Low temperature
2,0
30,0
High
Standard
0,9
11,0
High
Cooling
High temperature
1,0
14,0
High
Low temperature
0,6
2,0
Low
Ambient temp.
conditions DB/WB
(°C)
Indoor
Outdoor
20/–
7/6
27/–
21/15
20/–
–10/–10
27/19
35/24
32/23
43/26
21/15
21/15
Note :
• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
*
1
• During heating overload, the high temperature limit control operation is included.