6-1. Troubleshooting method
The list below summarizes check codes detected by various devices. Analyze the check code according to
where it is displayed and work out the nature of the problem in consultation with the list.
• When investigating a problem on the basis of a display provided on the indoor remote controller or central
remote controller See the “Remote control or main remote controller display” section of the list.
• When investigating a problem on the basis of a display provided on an outdoor unit - See the “Outdoor 7-
segment display” section of the list.
• When investigating a problem on the basis of a wireless remote controller-controlled indoor unit - See the
“Light sensor indicator light block” section of the list.
List of Check Codes (Indoor Unit)
(Check code detected by indoor unit)
Central control
or main remote
controller
display
Outdoor 7-segment display
Check code
Sub-code
Flash
Flash
Timer
Operation
Indicator light block
Display of receiving unit
Typical problem site
Description of Check code
: Lighting, : Flashing, : Goes off
ALT.: Flashing is alternately when there are two flashing LED
SIM: Simultaneous flashing when there are two flashing LED
E08
E08
Duplicated indoor
address
Duplicated indoor address
Indoor unit detects address identical to its own.
E04
—
—
Indoor-outdoor periodic
communication trouble
Signals are not being received from outdoor unit.
E03
—
—
Indoor-remote controller
periodic communication
trouble
Communication from remote controller or network
adaptor has been lost (so has central control
communication).
F01
—
—
ALT
Indoor heat exchanger
temperature sensor (TCJ)
trouble
Heat exchanger temperature sensor (TCJ) has
been open/short-circuited.
F02
—
—
ALT
Indoor heat exchanger
temperature sensor (TC2)
trouble
Heat exchanger temperature sensor (TC2) has
been open/short-circuited.
F03
—
—
ALT
Indoor heat exchanger
temperature sensor (TC1)
trouble
Heat exchanger temperature sensor (TC1) has
been open/short-circuited.
F10
—
—
ALT
Room air temperature sensor
(TA/TSA) trouble
Room air temperature sensor (TA) has been
open/short-circuited.
F11
—
—
ALT
Discharge air temperature
sensor (TF/TFA) trouble
Discharge air temperature sensor (TF) has been
open/short-circuited.
F29
—
—
SIM
P.C. board or other indoor
trouble
Open/Short-circuit of indoor air suction temperature
sensor (TRA) was detected.
L03
—
—
SIM Duplicated indoor group
header unit
There is more than one header unit in group.
L07
—
—
SIM
Connection of group control
cable to stand-alone indoor unit
There is at least one stand-alone indoor unit to
which group control cable is connected.
L08
L08
—
SIM Indoor group address not set
Address setting has not been performed for one or
more indoor units (also detected at outdoor unit end).
L09
—
—
SIM Indoor capacity not set
Capacity setting has not been performed for indoor
unit.
L20
—
—
SIM
Duplicated central control
address
There is duplication in central control address
setting.
P01
—
—
ALT Indoor AC fan trouble
Indoor AC fan trouble is detected (activation of fan
motor thermal relay).
P12
—
—
ALT Indoor DC fan trouble
Indoor DC fan trouble (e.g. overcurrent or lock-up)
is detected.
P31
—
—
ALT Other indoor unit trouble
Follower unit cannot be operated due to header unit
alarm (E03/L03/L07/L08).
P10
P10 Detected indoor unit
No.
ALT Indoor overflow trouble
Float switch has been activated.
L30
L30
Detected indoor unit
No.
SIM
Indoor external trouble input
(interlock)
Unit shutdown has been caused by external trouble
input (CN80).
E18
—
—
Trouble in periodic
communication between indoor
header and follower unit
Periodic communication between indoor header
and follower units cannot be maintained.
E10
—
—
Indoor inter-MCU
communication trouble
MCU communication between main controller and
motor microcontroller is failure.
E11
—
—
Communication check code
between Application control
kit and indoor unit
Communication check code between Application
control kit and indoor unit P.C. board.