9-9-11. Monitor Function of Remote Controller Switch
Switching to the service monitor mode
<Content>
The sensor temperature or operation status of the remote controller, indoor unit, or the outdoor unit can be
known by switching to the service monitor mode from the remote controller.
[Procedure]
<RBC-AMT32E>
1
Push + buttons simultaneously for 4 seconds or more
to call up the service monitor mode.
The service monitor goes on, and temperature of the CODE No. 00 is
firstly displayed.
2
Push the temperature setup
buttons to select the
CODE No. to be monitored.
For displayed codes, refer to the table next page.
3
Push button to determine the item to be monitored.
Then monitor the sensor temperature or operation status of indoor unit
and the outdoor unit in the corresponding refrigerant line.
4
Pushing button returns the display to the normal display.
<RBC-ASCU11-C>
1
Push the [menu] button for over 10 seconds.
2
Every pushing [
] [
] buttons, the indoor unit numbers in group control are
displayed successively.
3
Push the [OFF timer] button to confirm the selected indoor unit.
4
Every pushing [
] [
] buttons, CODE No. of the item is changed successively.
5
After you have finished checking, push the [ON/OFF] button to return to normal mode.
1,2
4
5
2, 4
3
1