Smart Manager
Engineering Book
36
-EN
5-1-3. Mode setting
<1> Smart Manager main / sub selection
When two Smart Manager units are used as a main unit and a sub unit with the same mode setting, set this bit to
OFF (Main) for one unit and to ON (Sub) for the other unit.
<2> Control group selection
These bits specify a group range used in the control group selection.
The Smart Manager for which control group selection is set controls only groups within the set group range.
To use the control group selection, set DS23-<2> to <5> and DS24-<5> to <6>.
<3> Central control / remote controller mode selection
Central control mode:
The Smart Manager is used as the central control device.
Remote controller mode: The Smart Manager is used as the remote controller.
<4> Central control Main / Sub selection
This setting is required when multiple Smart Manager units are used or another central control unit is used.
(1) Set this bit to OFF when one Smart Manager unit is used.
(2) When multiple central control units are used as a main unit and sub units, set to OFF (Main) for one unit and
set to ON (Sub) for other units.
<5> Timer input switching
These bits switch operation when the weekly timer has changed.
• Use (1) and (2) only in the remote control mode.
• When the control group selection is used, “All ON,” “All OFF” and “all indoor units” mean those within the set
group range.
<6> Buzzer
OFF: With buzzer sound
ON: Without buzzer sound
Control group selection
DS24-<6>
DS23
All groups
OFF
-
Group 1 ~ 16
ON
<2> ON
Group 17 ~ 32
ON
<3> ON
Group 33 ~ 48
ON
<4> ON
Group 49 ~ 64
ON
<5> ON
CENTRAL 1:Disables operation start / stop using the remote controller.
CENTRAL 2:Disables operation start / stop, operation mode switching, and temperature setting using the remote
controller.
Switch No.
<1>
<2>
<3>
Central controller operation
Timer
OFF
→
ON
Timer
ON
→
OFF
(1)
All ON
All OFF
OFF
OFF
OFF
(2)
No change
All OFF
ON
OFF
OFF
(3)
All indoor units are locally
controllable.
All indoor units CENTRAL 1
OFF
ON
OFF
(4)
All OFF and all indoor units to
be CENTRAL 1
ON
ON
OFF
(5)
All indoor units CENTRAL 2
OFF
OFF
ON
(6)
All OFF and all indoor units to
be CENTRAL 2
ON
OFF
ON