Smart Manager Setting
5-1. Smart Manager Setting
5-1-1. Central control address (group number) setting
• Central control addresses must be assigned to all air conditioners to be controlled.
• Under the control of the Smart Manager, central control address equals group number.
<Preparations for central control address (group number) setting>
• Turn on the power of all indoor and outdoor units.
• This Smart Manager or a standard wired remote controller is necessary for setting central control addresses.
• Terminate the operation of air conditioners, and then set central control addresses.
* To set central control addresses with the Smart Manager, initial communication with all connected indoor and
outdoor units must have been completed. Therefore, wait at least 10 minutes after power-on, and then start
central control address setting.
NOTE
If the address setting is made before the initial communication is completed, an address is not assigned to
some units.
• Connect terminals U1 and U2 in the outdoor unit (Header unit) to the relay connector of terminals U3 and U4.
• Set SW30-2 on the interface P.C. board of the outdoor unit (Header unit) to ON only for one system, and to OFF for
others.
* The location of SW30 is shown in the wiring diagram supplied with the outdoor unit.
<Setting central control addresses (group numbers)>
Use “manual setting from wired remote controller,” “manual setting,” or “automatic setting” to set central control
addresses.
A Manual setting from wired remote controller
Set central control addresses (group numbers) from a standard wired remote controller.
* The following setting procedure is described based on button operations of the wired remote controller RBC-
AMT32E.
1
Press the
button and
button simultaneously for at least 4 seconds.
(Note: Do not press the
button during setting.)
2
Press the
button to change the CODE No. 03.
3
Set central control addresses (group numbers) with the
buttons.
• Group numbers used for the Smart Manager are central control addresses (DN item 03).
• The effective address range is 1 to 64. However, there must be no duplicate address on the same line.
• An address value of 99 indicates that the address is not set.
4
Press the
button to fix the setting.
5
Press the
button to exit the address setting mode.
* This setting procedure may vary depending on the wired remote controller model.
* Perform these steps while air conditioners are not working.