E6581315
52
Inverter operating status 1 (FD01, FE01)
Inverter status 1 (current status): Communication Number FD01
Inverter status 1 (status immediately before the occurrence of a trip): Communication Number FE01
Bit Specifications
0
1
Remarks
0
Failure FL
No output
Output in progress
1
Failure
Not tripped
Tripped
Trip statuses include
and trip retention status.
2
Alarm
No alarm
Alarm issued
3
Reserved
-
-
4
Motor section (1 or 2)
(THR 2 selection)
Motor 1 (THR 1)
Motor 2 (THR 2)
5
PI control OFF
PI control
permitted
PI control
prohibited
6
Accelera-
tion/deceleration
pattern selection (1 or
2)
Acceleration/
deceleration
pattern 1 (AD 1)
Acceleration/
deceleration pat-
tern 2 (AD 2)
AD1 :
,
AD2 :
,
7
DC braking
OFF
Forced DC braking
8
Jog run
OFF
Jog run
9
Forward/reverse run
Forward run
Reverse run
10 Run/stop
Stop
Run
11 Coast stop (ST=OFF)
ST=ON
ST=OFF
12 Emergency stop
Not emergency
stop status
Emergency stop
status
13 Standby ST=ON
Start-up process
Standby
Standby: Initialization completed,
not failure stop status, not alarm
stop status (MOFF, LL forced
stop or forced stop due to a
momentary power failure),
ST=ON, and RUN=ON
14 Standby
Start-up process
Standby
Standby: Initialization completed,
not failure stop status, and not
alarm stop status (MOFF, LL
forced stop or forced stop due to
a momentary power failure)
15 Reserved
-
-