E6581315
40
7. Communication parameters
The settings of communication-related parameters can be changed from the operation panel and
the external controller (computer). Note that there are two types of parameters: parameters whose
settings take effect immediately after the setting and parameters whose settings do not take effect
until the inverter is turned back on or reset.
Com-
munica-
tion
Number.
Title
Function
Adjustment range
Unit
Default
setting
Valid
Reference
0800
Baud rate
(2-wire RS485)
0: 9600bps
1: 19200bps
2: 38400bps
-
1
After reset.
Section 7.1
0801
Parity (common)
0: Non parity
1: Even parity
2: Odd parity
-
1
After reset.
Section 7.1
0802
Inverter number
(common)
0-247
1
0
Real time
Section 7.2
0803
Communication
time-out time
(common)
0:OFF
1-100s
1s
0
Real time
Section 7.3
2-wire
4-wire
0
-
-
1
t alarm
-
2
Err5 trip
-
3
-
t alarm
4
t alarm
t alarm
5
Err5 trip
t alarm
6
-
Err5 trip
7
t alarm
Err5 trip
0804
Communication
time-out action
(common)
8
Err5 trip
Err5 trip
1
8
Real time
Section 7.3
0805
Send waiting time
(2-wire RS485)
0.00: Default
0.01-2.00s
0.01s
0.00
Real time
Section 7.4
0806
Inverter-to-inverter
communication
(2-
wire RS485)
0:Slave (issues a 0Hz command if some-
thing goes wrong with the master)
1:Slave (continues operation if something
goes wrong with the master)
2:Slave (trips for emergency stop if
something goes wrong with the master)
3:Master (sends a frequency command)
4:Master (sends an output frequency)
5.Master (sends a torque command)
6.Master (sends an output torque com-
mand)
-
0
After reset.
Chapter 6
0807
Protocol selection
(2-wire RS485)
0: TOSHIBA
1:MODBUS-RTU
-
0
After reset.
Chapter 3
0810
Frequency point
selection
0:Disabled
1:2-wire RS485
2:4-wire RS485
3:Communication add option
-
0
Real time
Section 6.1
0811
Point 1 setting
0-100%
-
0
Real time
0812
Point 1 frequency
0-
Hz
0.01Hz
0.0
Real time
0813
Point 2 setting
0-100%
-
100
Real time
0814
Point 2 frequency
0-
Hz
0.01Hz
60.0
Real time
Section 6.1
0820
Communication
speed
(4-wire RS485)
0: 9600bps
1: 19200bps
2: 38400bps
-
1
After reset.
Section 7.1
0825
Send waiting time
(4-wire RS485)
0.00: Normal
0.01-2.00s
0.01s
0.00
Real time
Section 7.4