INSTALLATION OF NEW REFRIGERANT 

AIR CONDITIONER

This air conditioner adopts the new HFC refrigerant (R410A) which does not deplete the ozone layer.

•  R410A refrigerant is apt to be affected by impurity such as water, oxidizing membrane, or oils because the 

pressure of R410A refrigerant is higher than that of the former refrigerant by approx. 1.6 times.

  Accompanied with adoption of the new refrigerant, refrigerating oil has been also changed.
  Therefore pay attention so that water, dust, former refrigerant, or refrigerating oil does not enter into the 

refrigerating cycle of the new refrigerant air conditioner during installation work.

•  To prevent from mixing of refrigerant or refrigerating oil, the size of charge port of the main unit or connecting 

section of installation tool differs from that of the air conditioner for the former refrigerant.

  Accordingly the exclusive tools are required for the new refrigerant (R410A) as shown below.
•  For connecting pipes, use the new and clean piping materials so that water or dust does not enter.

 

„

Required tools and cautions on handling

It is necessary to prepare the tools and parts as described below for the installation work.
The tools and parts which will be newly prepared in the following items should be restricted to the exclusive 
use.

Explanation of symbols

 :  Newly prepared (It is necessary to use it properly exclusive to R410A separated from those for R22 or 

R407C.)

 :  Former tool is available.

Used tools

Usage

Proper use of tools/parts

Gauge manifold

Vacuuming or charging of
refrigerant and operation check

Newly prepared, Exclusive to R410A

Charging hose

Newly prepared, Exclusive to R410A

Gas leak detector

Checks gas leak

Newly prepared

Vacuum pump

Vacuum drying

Usable if a counter-

fl

 ow preventive adapter is attached

Vacuum pump with counter-

fl

 ow 

preventive adapter

Vacuum drying

: R22 (Existing article)

Bender

Bending processing of pipes

: R22 (Existing article)

Refrigerant recovery device

Recovers refrigerant

Exclusive to R410A

Pipe cutter

Cuts pipes

: R22 (Existing article)

Refrigerant cylinder

Charges refrigerant

Exclusive to R410A

ID : Refrigerant name entered

Brazing machine/
Nitrogen gas cylinder

Brazing of pipes

: R22 (Existing article)

Refrigerant charging balance

Charges refrigerant

: R22 (Existing article)

 

„

Refrigerant piping

•  Piping material used for the conventional refrigerant cannot be used.
•  Use copper pipe with 0.8mm or more thickness for Ø6.4, Ø9.5, Ø12.7mm.
  Use copper pipe with 1.0mm or more thickness for Ø15.9mm, Ø19.1mm, Ø22.2mm or more.
•  Use clean and new pipes for the refrigerant pipes and perform piping work so that water or dust does not 

contaminate the refrigerant.

3

SELECTION OF INSTALLATION PLACE

 CAUTION

Do not install the air conditioner at place where combustible gas may leak.

If gas leaks and is collected at surrounding the unit, the production of 

fi

 re may be caused.

Cautions for Installation at a Place with the Quiet Background Sound

As the Flow Selector unit incorporates the solenoid valve, the refrigerant sound or the operating sound of the
solenoid valve such as “Bushuu...” generates when exchanging between cooling and heating mode and during
defrost operation. Therefore, avoid installing the unit at a place with quiet background sound as follows.
  (1)  Rooms with quiet background sound such as bedroom, hospital, or room in a hotel.
  (2)  Rooms which have no ceiling and a fabric does not block the residence space from the Flow Selector 

unit.

  (3)  Rooms which have opening port at the ceiling.

   

Flow selector unit

Indoor unit

10m or more

When installing the unit at the above places, separate the unit from the indoor unit (more than 10 m) and install 
the unit at a place so that sound does not transmit into the room such as in the corridor ceiling.
And take sound proof measure, such as covering around the Flow Selector unit with the sound proo

fi

 ng 

materials.

Upon customer’s approval, install the air conditioner at a place where satis

fi

 es the following conditions.

•  Place where it can be installed horizontally.
•  Place which can reserve a service space for safe maintenance or check.
•  Place where there is no problem even if the drained water 

fl

 ows.

Apply electric insulation between metal section of the building and metal section of the air conditioner in 
conformance with the Local Regulation.
Avoid the following places.

•  Salty place (seaside area) or place with much gas sul

fi

 de (hot spring area)

  (If selecting such a place, a special maintenance is required.)
•  Place where oil (including machine oil), steam, oil smoke or corrosive gas generates.
•  Place where a device generating high frequency (inverter, non-utility generator, medical apparatus, or 

communication equipment) is set. (A bad in

fl

 uence may generate by malfunction of the air conditioner, control 

trouble, or noise for such equipment.)

Содержание RBM-Y1801F4PE

Страница 1: ...INSTALLATION MANUAL 1 English RBM Y1801F4PE RBM Y1801F6PE Installation Manual Multi Port Flow Selector Unit ...

Страница 2: ...hoose one according to the capacity of the units ADOPTION OF NEW REFRIGERANT This Super Heat Recovery Multi Air Conditioner is a new type which adopts a new refrigerant HFC R410A instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer Be sure to use an indoor or outdoor unit in combination with the new refrigerant CONTENTS Accessory parts and Parts to be proc...

Страница 3: ...Ø22 2 Ø15 9 1 1 Ø22 2 Ø12 7 1 1 Ø22 2 Ø9 5 1 1 Binding band L300 2 2 For fixing heat insulation of flexible hose Binding band L200 16 24 For fixing heat insulating pipes Binding band L100 5 7 For fixing clamp filters Clamp filter 5 7 For reducing electrical noise of communication wires and float switch wire of drain pump locally procured Cable clamp 6 8 For fixing indoor unit communication cables ...

Страница 4: ...t to enter any gaseous matter other than the specified refrigerant into the refrigeration cycle If air or any other gas is mixed in the refrigerant the gas pressure in the refrigeration cycle becomes abnormally high and it as a result causes pipe burst and injuries on persons Do not modify this unit by removing any of the safety guards or by by passing any of the safety interlock switches Exposure...

Страница 5: ...gerant piping Piping material used for the conventional refrigerant cannot be used Use copper pipe with 0 8mm or more thickness for Ø6 4 Ø9 5 Ø12 7mm Use copper pipe with 1 0mm or more thickness for Ø15 9mm Ø19 1mm Ø22 2mm or more Use clean and new pipes for the refrigerant pipes and perform piping work so that water or dust does not contaminate the refrigerant 3 SELECTION OF INSTALLATION PLACE CA...

Страница 6: ...ow Selector unit Procure hanging bolts washer and nuts for installing the Flow Selector unit these are not supplied Hanging bolt M10 or W3 8 4 pieces Nut M10 or W3 8 12 pieces Installation under high humidity atmosphere In some cases including the rainy season especially inside of the ceiling may become high humidity atmosphere dew point temperature 23 C or higher 1 Installation to inside of the c...

Страница 7: ...al level of installed ceiling correctly in order to prevent vibration of ceiling board Attach the nuts and the M10 flat washers to the hanging bolt Put washers at up and down of the hanging bracket of the Flow Selector unit to hang down the Flow Selector unit Check that four sides are horizontal with a level gauge Horizontal degree Within 5 mm Hanging bolt W3 8 or M10 70 mm or less M10 flat washer...

Страница 8: ...o the unit with proper heat insulation Improper heat insulation will cause condensation to form The drain pipe must be sloping downward at an angle of 1 100 or more and do not run the pipe up and down arched shape or allow it to form traps Doing so may cause abnormal sounds Restrict the length of the traversing drain pipe to 20 meters or less For a long pipe provide support brackets at intervals o...

Страница 9: ...es not leak from the connect the pipes Check port Plastic container to pour water 6 REFRIGERANT PIPING WARNING If refrigerant gas has leaked during the installation work ventilate the room immediately If the leaked refrigerant gas comes in contact with fire noxious gas may be generated After the installation work confirm that refrigerant gas does not leak If refrigerant gas leaks into the room and...

Страница 10: ... connection per one port Outdoor unit side pipe size 1 Total capacity codes of indoor units at the downstream side Outdoor unit side Upstream Equivalent to capacity Equivalent to HP Suction gas pipe Discharge gas pipe Liquid pipe Below 18 0 Below 6 4 Ø15 9 Ø12 7 Ø9 5 18 0 to below 34 0 6 4 to below 12 2 Ø22 2 Ø19 1 Ø12 7 34 0 to below 45 5 12 2 to below 16 2 Ø28 6 Ø22 2 Ø15 9 45 5 to below 56 5 16...

Страница 11: ...re of the pipe The pipe exposed to the outside causes water leak 7 ELECTRICAL CONNECTION CAUTION If incorrect incomplete wiring is carried out it will cause an electrical fire or smoke Use the cord clamps attached to the product Do not damage or scratch the conductive core and inner insulator of power and communication wires when peeling them Use the power cord and communication wire of specified ...

Страница 12: ...pply terminal block Cable clamp Accessory Clamp all cables Terminal on PCB for Communication wiring Communication wire Clamp the communication wire Detail a For each communication wire attach the Clamp filter accessory as the picture below Clamp filter Accessory Hook 2 nails Communication wire locally procured 1 turn Attach round shaped terminal locally procured Clamp filter Accessory Binding band...

Страница 13: ...ng wires to the terminal 2 mm or less Communication wire Communication wiring A B A B Terminal block for remote controller wiring of indoor unit Communication wires locally procured FS unit terminal on PCB It s possible to come out the communication wires on the right side Cable clamp Accessory Clamp all cables Communication wire ...

Страница 14: ...r power switch Header outdoor unit Follower outdoor unit Earth terminal Earth terminal Control wiring between outdoor units Control wiring between indoor and outdoor units Control wiring between indoor units Indoor unit Indoor unit Indoor unit Indoor unit Earth Earth Earth Earth Pull box Pull box Pull box Remote controller Remote controller Remote controller Earth Earth Indoor unit FS unit power s...

Страница 15: ...r setup of address When connecting the indoor units to a branch of FS unit it is possible to connect with multiple groups and connect individually Indoor unit Piping FS unit Remote controller Group control How to set up CODE No 0E It is necessary to set up in case of the group control 2 4 1 3 5 1 Push and hold the and buttons at the same time for more than 4 seconds is displayed in the UNIT No win...

Страница 16: ...Group control Group control Indoor unit In case of connecting Drain pump locally procured It s available to connect the operation off signal input cable of float switch At that time the cable is taken from the hole on the control box bottom side and connect to CN34 on PC board of unit No 1 showing 1 on the label Be sure to connect the energized indoor unit to unit No 1 of FS unit Attach Rubber bus...

Страница 17: ...1118430099 TOSHIBA CARRIER THAILAND CO LTD 144 9 MOO 5 BANGKADI INDUSTRIAL PARK TIVANON ROAD TAMBOL BANGKADI AMPHUR MUANG PATHUMTHANI 12000 THAILAND ...

Отзывы: