To erase the fault code history. 

1)

 

Press the “                             [F2]” button whilst 
the list of alarm codes is displayed. 
 
 
 
 

2)

 

When the display has changed press 
the “                                [F1]” button. 

  

Code 

Description 

E01 

No communication between remote controller and indoor unit. (Master indoor unit maybe switched off) 

E02 

Local controller failure – unable to transmit 

E03 

Master indoor unit receives no data to A-B (Could also show as E01 fault) 

E04 

Indoor unit (except twin slave) receives no communications from outdoor unit; can also include klixon on discharge pipe of outdoor unit 

E08 

Duplicated indoor unit address 

E09 

2 local controllers connected on a group – both configured as masters 

E10 

Indoor unit PCB failure 

E18 

Communications failure between master indoor unit and slave indoor unit or units 

F01 

Indoor unit TCJ (Liquid) sensor error (Open or Closed circuit – resistance is measured in kΩ  

F02 

Indoor unit TC2 (Vapour) sensor error (Open or Closed circuit – resistance is measured in kΩ  

F04 

Outdoor unit TD (Discharge) sensor error (Open or Closed circuit – resistance is measured in kΩ 

F06 

Outdoor unit TE (Coil) sensor error (Open or Closed circuit – resistance is measured in kΩ 

F08 

Outdoor unit TO (Ambient) sensor error (Open or Closed circuit – resistance is measured in kΩ 

F10 

Indoor unit TA (Return Air) sensor error (Open or Closed circuit – resistance is measured in kΩ  

F29 

Indoor unit PCB failure 

H01 

Outdoor unit Inverter compressor over current detected 

H02 

Master outdoor unit over current detected shortly after start up 

H03 

Current detected on Master outdoor unit whilst idle 

H06 

Outdoor unit Low pressure detected by Ps sensor (0.2 bar – 2.9 psig) 

L03 

Indoor unit Duplicated master indoor units in a group 

L07 

Indoor unit in a group of units previously addressed as a single unit – check addressing 

L08 

Indoor units addresses not set – check addressing 

L09 

Indoor units capacity not set (check DN Code 11) 

L29 

Outdoor unit IPDU error (Number of detected IPDU units is reduced) 

L30 

Input on indoor PCB CN80 circuit for 1 minute 

L31 

Outdoor unit PCB error 

P01 

Indoor unit fan motor error 

P03 

Outdoor unit High discharge temperature (TD1 exceeded 115

 

o

C) 

P04 

Outdoor unit High pressure switch activated (Detected by high temperature on TE sensor on digital/super digital inverter units) 

P07 

Outdoor unit PCB heat sink overheated (Temperature over 90 

o

C recorded) 

P10 

Indoor unit Float switch activated 

P12 

Indoor unit fan motor error – detected by feedback circuit 

P19 

Wrong change in temperature recorded (4 way valve error) 

P22 

Outdoor unit fan motor IPDU error  

P26 

Outdoor unit Giant transistor short circuit 

P29 

Outdoor unit Compressor error detected by feedback circuit 

P30 

Indoor unit Group control follower unit error / duplicated central control addresses 

P31 

Indoor unit PCB error 

C05 

Central control Sending error in TCC-Link central control device 

C06 

Central control Receive error in TCC-Link central control device 

C12 

Batch alarm for general purpose equipment interface 

More detailed listings are available in the technical handbook or relevant service literature 

Содержание RBC-AMS51E

Страница 1: ...Pocket Quick Reference Guide On the TOSHIBA RBC AMS51E Remote Controller ...

Страница 2: ...nto the on board menu of the remote controller Controller Layout 1 ON OFF button 5 F1 button Illuminates when system is running Varies its functions according to the setting screen 2 Temperature up button 6 F2 button Used in the menu screen to select Varies its functions according to menu items the setting screen 3 Temperature down button 7 Cancel button Used in the menu screen to select Functions...

Страница 3: ...n 2 Press and hold the button and the button at the same time for more than 4 seconds to display the Field setting menu 3 Scroll down to item 3 using the button 4 Press F2 A list of the latest 10 alarm codes along with date time and unit are displayed The oldest data are deleted in order to record the newest the date and time when the error occured for the first time are displayed for any repeated...

Страница 4: ...Master outdoor unit over current detected shortly after start up H03 Current detected on Master outdoor unit whilst idle H06 Outdoor unit Low pressure detected by Ps sensor 0 2 bar 2 9 psig L03 Indoor unit Duplicated master indoor units in a group L07 Indoor unit in a group of units previously addressed as a single unit check addressing L08 Indoor units addresses not set check addressing L09 Indoo...

Страница 5: ... the temperature measured by the TO ambient air sensor within the outdoor unit 4 Display s the remaining time until the filter sign is displayed 5 Display s the accumulated operating time of the system To access the second level of data display 5 Press the button to display the Menu screen 6 Press and hold the button and the button at the same time for more than 4 seconds to display the Field sett...

Страница 6: ... If fitted o C 73 Fan Speed Upper rpm F1 Compressor Run Time x 100h VRF indoor data for Mini SMMS SMMS SMMSI SHRM equipment Code Indoor Data Code Indoor Data 00 Room Temp Control Temp o C 06 Indoor Discharge Temp If Used o C 01 Room Temp Remote Controller o C 08 PMV Position 0 10 02 TA Return Air Temp o C 0A Number of Connected Indoor Units No 03 TCJ Coil Liquid Temp o C 0b Indoor Capacity x 10 HP...

Страница 7: ...mp o C 6 Compressor IPDU 3 Heat Sink Temp o C 7 TE2 Outdoor Coil Temp o C 7 Outdoor Fan IPDU Heat Sink Temp o C 8 TL Liquid Temp o C 8 Heating Cooling Recovery Controlled 9 TO Outdoor Ambient Temp o C 9 Pressure release A PMV 1 2 Opening A Discharge Temp Release B PMV 4 Opening B Follower Unit Release C Compressor 1 Current A F Outdoor Unit Size HP D Compressor 2 Current A Note Would be replaced w...

Страница 8: ...s and hold the button and the button at the same time for more than 4 seconds to display the Field setting menu 3 Scroll down to item 5 using the button 4 Press F2 Code DN 10 will be highlighted on the left of the display 5 Scroll the Code DN to 32 using the buttons 6 When Code DN 32 is highlighted on the left press F2 to highlight Data on the right 7 Change Data from 0000 to 0001 by pressing the ...

Страница 9: ... to display the Field setting menu 10 Scroll down to item 5 using the button 11 Press F2 Code DN 10 will be highlighted on the left of the display 12 Scroll the Code DN to 28 using the buttons 13 When Code DN 32 is highlighted on the left press F2 to highlight Data on the right 14 Change Data from 0000 to 0001 by pressing the 15 Press follow on screen instructions ...

Страница 10: ... then press Set F2 button 4 Press the button to select the year month date time Press the F1 or F2 button to set the value 5 Press the button Setting ON and OFF Times scheduled operations 1 Press the button to display the Menu screen 2 Press the button to select option 5 Schedule timer then press the Set F2 button 3 Press the F1 button to turn On or F2 to turn off the schedule timer ...

Страница 11: ...ect ON to set start time and set temperature settings Select OFF to set the stop time indicates that item has not been set 4 Press the F2 button to select time or temperature When is displayed time or temperature cannot be selected 5 Press the button to set time or temperature 6 Press the F1 to program the next pattern Up to 8 patterns per day can be programmed 7 Press the button Screen returns to...

Страница 12: ...dule for the day selected is deleted 3 Press the F2 button to Return to the Condition setting screen To copy the settings of the previous day 1 Press the button on the day selection screen 2 Press the F1 button The schedule for the previous day is copied 3 Press the F2 button to Return to the Condition setting screen ...

Страница 13: ...F2 button Energy Saving Ratio 1 Press the button to Select option 2 Energy Saving Ratio 2 Press the F1 or F2 to set the value The energy saving ratio can be set within the range from 50 to 100 by 1 increments The lower the value is set the higher the power saving effect Item Function 1 Energy Saving Operation Perform the power saving operation of the air conditioner 2 Set temp Range limit Set the ...

Страница 14: ...rgy Saving Temperature Setting 1 Press the buttons to Select 2 Set temp range limit on the Energy Saving Screen and then press the F2 button 2 Press the button to set the temperature Press the F1 or F2 button to set the value 3 Press the button The screen returns to the Energy Saving Screen Setting appears and then the screen returns to the Energy saving operations screen ...

Страница 15: ... individual operation for the ventilation unit is not actived 2 Fan Speed or 3 Mode 4 24H Ventilation off is available only for the air conditioning system using the Toshiba Air to Air Heat Exchanger VN M HE series appears on the detailed display during the ventilation operation when the ventilation unit other than the Toshiba Air to Air Heat Exchanger VN M HE series is used and the individual ope...

Страница 16: ... 0844 800 0250 Toshiba Air Conditioning 24 7 technical support 0870 843 0333 Text back service 07624 803 017 Type fault code in lower case no spaces Cool Designs Ltd reserves the right to change the product specifications data and images without notice ...

Отзывы: