VRF Outdoor data for SMMSI equipment
Code
Outdoor Data
Code
Outdoor Data
*0
Pd – High Pressure Sensor (MPa)
#0
Compressor 1 Revolutions (rps)
*1
Ps – Low Pressure Sensor (MPa)
#1
Compressor 2 Revolutions (rps)
*2
Td1 – Compressor 1 Discharge Temp. (
o
C)
#2
Compressor 3 Revolutions (rps)
*3
Td2 – Compressor 2 Discharge Temp. (
o
C)
#3
Outdoor Fan Mode
*4
Td3 – Compressor 3 Discharge Temp. (
o
C)
#4
Compressor IPDU 1 Heat Sink Temp. (
o
C)
*5
TS – Suction Temp. (
o
C)
#5
Compressor IPDU 2 Heat Sink Temp. (
o
C)
*6
TE1 – Outdoor Coil Temp. (
o
C)
#6
Compressor IPDU 3 Heat Sink Temp. (
o
C)
*7
TE2 – Outdoor Coil Temp. (
o
C)
#7
Outdoor Fan IPDU Heat Sink Temp. (
o
C)
*8
TL – Liquid Temp. (
o
C)
#8
Heating / Cooling Recovery Controlled
*9
TO – Outdoor Ambient Temp. (
o
C)
#9
Pressure release
*A
PMV 1 + 2 Opening
#A
Discharge Temp. Release
*B
PMV 4 Opening
#B
Follower Unit Release
*C
Compressor 1 Current (A)
#F
Outdoor Unit Size (HP)
*D
Compressor 2 Current (A)
Note. * Would be replaced with 1, 2, 3 or 4 to
obtain data from respective outdoor unit.
# would be replaced with either 5, 6, 7, 8 to
obtain data from outdoor units 1,2,3 or 4
*E
Compressor 3 Current (A)
*F
Outdoor Fan Current (A)
For more detailed descriptions please refer to the relevant technical service manual.
NOTES: