– 108 –
Concave part
PMV main unit
Positioning projection
PMV coil
Bell mouth
Discharge
port cabinet
Fan guard
PT2P Ø3
㬍
14 and washer
Hooking claw
Straight line ofbell moouth
No.
11
12
Part name
PMV coil
Fan guard
Procedure
1. Detachment
1) Carry out work of item 1 of
c
.
2) Turn the coil while pulling upward and then
remove the coil from the PMV main unit.
2. Attachment
1) Surely match the positioning projection of
the coil with the concave part of PMV main
unit and then fix it.
1. Detachment
1) Carry out works of item 1 of
c
and 1 of
d
.
REQUIREMENT
To prevent scratch on the product, carry out
the work on cardboard, cloth, etc.
2) Remove the discharge port cabinet and then
put on it so that the fan guard side directs
downward.
3) Remove the screw for the bell mouth and
fan guard.
(PT2P Ø3 × 14 and washer, 4 pcs.)
4) Remove the hooking claws (8 positions) of
the fan guard.
2. Attachment
1) Push the hooking claws (8 positions) with
hands from the front side to fix the claws.
2) Attach the bell mouth fixed with screws and
washers.
(PT2P Ø3 × 14 and washer, 4 pcs.)
REQUIREMENT
Check that all the hooking claws are fixed at
the specified positions.
Remarks