– 83 –
- 11 -
Set the out margin of the anchor bolt to 15 mm or less.
•
When water is to be drained through the drain hose,
attach the following drain nipple and waterproof
rubber cap, and use the drain hose (Inner diam:
16 mm) sold on the market. Also seal knockout hole
and the screws securely with silicone material, etc.,
to prevent water from leaking.
Some conditions may cause dewing or dripping of
water.
•
When collectively draining discharged water
completely, use a drain pan.
For Reference
If a heating operation is to be continuously performed for
a long time under the condition that the outdoor
temperature is 0 °C or lower, draining defrosted water
may be difficult due to the bottom plate freezing,
resulting in trouble with the cabinet or fan.
It is recommended to procure an anti-freeze heater
locally in order to safely install the air conditioner.
For details, contact the dealer.
GOOD
Fixing leg
Absorb vibration
with vibration-proof
rubber pads
Foundation
GOOD
Bottom plate of
outdoor unit
Foundation
Support the bottom surface of
the fixing leg that is in contact
with and underneath the bottom
plate of the outdoor unit.
NO GOOD
If only the
end of the
fixing leg is
supported, it
may deform.
Do not support
the outdoor unit
only with the
fixing leg.
Foundation
15 or less
Drain nipple
Waterproof rubber cap
Waterproof rubber cap
Drain nipple
Knockout hole
5
REFRIGERANT PIPING
Knockout of Pipe Cover
Knockout procedure
• The indoor/outdoor connecting pipes can be
connected in 4 directions.
Take off the knockout part of the pipe cover through
which pipes or wires will pass through the base plate.
• Detach the pipe cover and tap on the knockout section
a few times with the shank of a screwdriver. A
knockout hole can easily be punched.
• After punching out the knockout hole, remove burrs
from the hole and then install the supplied protective
bush and guard material around the passage hole to
protect wires and pipes.
Be sure to attach the pipe covers after pipes have
been connected. Cut the slits under the pipe covers to
facilitate the installation.
After connecting the pipes, be sure to mount the pipe
cover. The pipe cover is easily mounted by cutting off
the slit at the lower part of the pipe cover.
* Be sure to wear heavy work gloves while working.
Rear direction
Pipe cover
Side direction
Down direction
Front direction
Supplied protective bush
Supplied passage hole guard material
* Attach the guard material securely
so that it does not come loose.
EN-21
EN-22