– 82 –
- 10 -
• When using an air conditioner under low outside
temperature conditions (Outside temp: -5 °C or
lower) in COOL mode, prepare a duct or wind
shield so that it is not affected by the wind.
• When installing the unit in an area where
snowfalls may be heavy, take steps to prevent the
unit from being adversely affected by the fallen or
accumulated snow.
• Either make the foundation higher or install a
stand (which is high enough to ensure that the
unit will be above the fallen or accumulated
snow) and place the unit on it.
• Attach a snow shield (locally procured).
Necessary Space for Installation
(Unit: mm)
Obstacle at rear side
Upper side is free
1.
Single unit installation
2.
Obstacles on both right and left sides
3.
Serial installation of two or more units
Obstacle also above unit
Obstacle in front
Above unit is free
1.
Single unit installation
<Example>
Wind shield
Wind shield
Wind shield
150 or
mor
e
20
0 o
r
more
150 or
more
300 or
more
The height of the
obstacle should be
lower than the height
of the outdoor unit.
150 or
more
300 or
more
300 or
more
300 or
more
The height of the obstacle should be lower than
the height of the outdoor unit.
200 or more
150 or
more
5
00 o
r
more
500
o
r
more
2.
Serial installation of two or more units
Obstacle also at the above unit
Obstacles in both front and rear of unit
Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of the
unit, should be lower than the height of the outdoor unit.
Standard installation
1.
Single unit installation
2.
Serial installation of two or more units
Serial installation in front and rear
Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of the
unit should be lower than the height of the outdoor unit.
Standard installation
Installation of Outdoor Unit
• Before installation, check the strength and
horizontalness of the base so that abnormal sounds
do not emanate.
• According to the following base diagram, fix the base
firmly with the anchor bolts.
(Anchor bolt, nut: M10 x 4 pairs)
• As shown in the figure below, install the foundation
and vibration-proof rubber pads to directly support the
bottom surface of the fixing leg that is in contact with
and underneath the bottom plate of the outdoor unit.
* When installing the foundation for an outdoor unit with
downward piping, consider the piping work.
1,
000
o
r
mor
e
1,
000
o
r
mo
re
1,000 or
more
1
50 or
more
1,
00
0 or
more
20
0 o
r
more
1,
00
0 o
r
more
300 or
more
300 or
more
1,000 or
more
300 or
more
1,500 or
more
2,000 or
more
200 or
more
150
150
600
525
45
365
400
Drain nipple
mounting hole
Drain hole
Drain hole
EN-19
EN-20