10. ON-SITE SETTING AND OTHERS
1. Indoor Unit
1.1 Test Operation Setting by Remote Controller only.
The lamps on the unit blink during test operation.
<Wired remote controller>
1
Push
TEST
on the remote controller for 4 seconds. When “TEST” appears on the LCD, push
ON / OFF
.
• “TEST” appears on the LCD during test operation.
• Test operation disables temperature control, but allows fan speed control.
• An instruction of fixed frequency is issued for cooling and heating of test operation.
• Alarm detection is performed as usual.
The test operation mode must be used for its original purpose only, because it stresses the air conditioner.
2
Choose COOL or HEAT mode only for test operation.
• (Note) Outdoor unit does not run about 3 minutes after power on or operation stop.
3
Repush
TEST
after test operation and confirm that “TEST” disappears from the LCD.
Wired remote controller has 60-minute timer reset function to prevent continuous test operation.