– 62 –
∗∗∗∗∗
3 Writing Setting Data in EEPROM
(The data of the EEPROM on the service board is the factory setting data.)
1) Push
SET
,
CL
, and
TEST
on the remote controller simultaneously for 4 seconds or more.
1
(see page 62)
∗
In the group control mode, the header unit number is displayed first.
(If auto address setting mode is canceled in 2-2) a) ii) above, UNIT No. is
indicated.)
At this time, code (DN)
is displayed, and the fan of the selected indoor unit runs, its louver swings,
and the OPERATION, TIMER, and PREPARING lamps blink.
2) Each pushing of
UNIT LOUVER
indicates indoor unit number in the group sequentially.
2
Specify indoor unit number whose board is replaced. (This operation is disabled if UNIT No. is
ALL.
)
3) Each pushing of TEMP.
/
buttons increments or decrements DN.
3
4) Set the indoor unit capacity first.
The factory setting data is written in the EEPROM.
i) Change DN to
with TEMP.
/
buttons.
ii) Set the indoor unit capacity with TIME
/
buttons. 4 (for example, “0012” for 80 class)
See the table (page 63).
iii) Push
SET
Indication on the LCD shows normal operation.
iv) Push
TEST
to return the operation mode to normal OFF.
6
(It takes about one minute until remote controller operation is enabled.)
5) Write the data set after installation (such as address) in the EEPROM.
Repeat steps 1) and 2) above.
6) Specify DN
with TEMP.
/
buttons.
(Setting of filter sign ON time)
7) Check the displayed data comparing the content written down
in
*1
(page 63).
i) If the data is incorrect, change it with TIME
/
buttons to the data of the memo, and then push
SET
Indication on the LCD shows normal operation.
ii) No operation is required for the same data.
8) Change DN with TEMP.
/
buttons.
In the same way as above, check the displayed data comparing the content of the memo.
If the data is incorrect, change it to the data of the memo.
9) Repeat steps 7) and 8) above.
10) When the setting is completed, push
TEST
to return the operation mode to normal OFF.
6
(It takes about
one minute until remote controller operation is enabled.)
* DN =
to
)>
. DN does not always shift sequentially. Even if data is updated and
SET
button is
pushed by mistake, the previous data can be restored with
CL
button unless DN is changed.