– 88 –
[F02 error]
Correct connection of connector.
Are characteristics of
TC sensor resistance value normal?
Is connection of TC sensor connector
(CN101 on Indoor P.C. board) correct?
∗
Refer to Characteristics-2.
Replace TC sensor.
Check indoor P.C. board (MCC-1570).
Defect
→
Replace
Correct connection of connector.
Are characteristics of
TCJ sensor resistance value normal?
Is connection of TCJ sensor connector
(CN102 on Indoor P.C. board) correct?
∗
Refer to TCJ sensor
(Temperature-Resistance value characteristic table)
Replace TCJ sensor.
Check indoor main P.C. board (MCC-1570).
Defect
→
Replace
YES
YES
YES
YES
NO
NO
NO
NO
[F01 error]