How to open the valve
Open or close the valve.
Liquid side, gas side
Open the valve with hexagon wrench.
[Hexagonal wrench is required.]
Hexagonal wrench size
Liquid side
Gas side
SM30
4 mm
4 mm
SM40
4 mm
4 mm
Valve handling precautions
• Open the valve stem until it strikes the stopper.
It is unnecessary to apply further force.
• Securely tighten the cap with a torque wrench.
Cap tightening torque
Valve size
Ø6.4 mm
14 to 18 N•m
(1.4 to 1.8 kgf•m)
Ø9.5 mm
14 to 18 N•m
(1.4 to 1.8 kgf•m)
Ø12.7 mm
33 to 42 N•m
(3.3 to 4.2 kgf•m)
Charge port
14 to 18 N•m
(1.4 to 1.8 kgf•m)
■
Replenishing refrigerant
This model is a 15 m chargeless type that does not
need to have its refrigerant replenished for refrigerant
pipes up to 15 m. When a refrigerant pipe longer than
15 m is used, add the specified amount of refrigerant.
Refrigerant replenishing procedure
1. After vacuuming the refrigerant pipe, close the
valves and then charge the refrigerant while the air
conditioner is not working.
2. When the refrigerant cannot be charged to the
specified amount, charge the required amount of
refrigerant from the charge port of the valve on the
gas side during cooling.
Requirement for replenishing refrigerant
Replenish liquid refrigerant.
When gaseous refrigerant is replenished, the
refrigerant composition varies, which disables normal
operation.
Adding additional refrigerant
16~20 m: L
SM30, SM40
20 g × (L-15)
• L: Pipe length
• The refrigerant need not be reduced for a 15 meter
(or less) refrigerant pipe.
7
Electrical
work
CAUTION
• An installation fuse must be used for the power supply
line of this air conditioner.
• Incorrect / incomplete wiring may lead to an electrical
fi
re or smoke.
• Prepare an exclusive power supply for the air
conditioner.
• This product can be connected to the mains power.
Fixed wire connections:
A switch that disconnects all poles and has a contact
separation of at least 3 mm must be incorporated in
the
fi
xed wiring.
• Be sure to use the cord clamps attached to the
product.
• Do not damage or scratch the conductive core or inner
insulator of the power and system interconnection
wires when peeling them.
• Use the power and system interconnection wires with
speci
fi
ed thicknesses, speci
fi
ed types and protective
devices required.
1
Remove valve cover screw.
2
Pull the valve cover downward to remove it.
Valve cover
Power supply wire
System
interconnection
wires
■
Wiring between indoor unit
and outdoor unit
The dashed lines show on-site wiring.
L
N
1
2
3
1
2
3
(Main circuit)
Input power
Circuit
breaker
Earth
Outdoor unit
Indoor unit
Remote
controller
(System
interconnection wires)
• Connect the system interconnection wires to the
identical terminal numbers on the terminal block of
each unit.
Incorrect connection may cause a failure.
For the air conditioner, connect a power wire with the
following specifications.
Model RAV-
SM30
SM40
Power supply
220-240 V~, 50 Hz
220 V~, 60 Hz
Maximum running current
8.5 A
10.0 A
Installation fuse rating
11.0 A
12.0 A
Power supply wire
H07 RN-F or 60245 IEC 66
(1.5 mm
2
or more)
System interconnection
wires
H07 RN-F or 60245 IEC 66
(1.0 mm
2
or more)