– 42 –
Indoor unit data
Item code
01
02
03
04
F2
F3
Data name
Room temperature
(Remote controller)
Indoor suction temperature (TA)
Indoor heat exchanger (Coil)
temperature (TCJ)
Indoor heat exchanger (Coil)
temperature (TC)
Indoor fan calculated operation time
Filter sign time
Unit
°C
°C
°C
°C
×100h
×1h
Outdoor unit data
Item code
60
61
62
63
65
6A
6D
70
72
73
F1
Data name
Outdoor heat exchanger (Coil) temperature (TE)
Outside temperature (TO)
Compressor discharge temperature (TD)
Compressor suction temperature (TS)
Heat sink temperature (THS)
Operation current (× 1/10)
Outdoor heat exchanger (Coil) temperature (TL)
Compressor operation frequency
Outdoor fan revolution frequency (Lower)
Outdoor fan revolution frequency (Upper)
Compressor calculated operation time
Unit
°C
°C
°C
°C
°C
A
°C
rps
rpm
rpm
×100h
<Operation procedure>
1 2 3 4
Returned to usual display
2
4
1
3
SET
TIME
TIMER SET
TEST
FILTER
LL
RESET
TEMP.
CL
FAN
SAVE
A
A
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
T
8-2-3. Monitor Function of Remote Controller Switch
Calling of sensor temperature display
<Contents>
Each data of the remote controller, indoor unit and outdoor unit can be understood by calling the service
monitor mode from the remote controller.
<Procedure>
1
Push
TEST
+
CL
buttons simultaneously for 4 seconds to
call the service monitor mode.
The service monitor goes on, the master indoor unit No. is
displayed at first and then the temperature of item code
00
is
displayed.
Ø
2
Push temperature set
TEMP.
buttons and then change
the item code of data to be monitored.
The item code list is shown below.
Ø
3
Push
UNIT LOUVER
button to select the indoor unit to be monitored.
Each data of the indoor unit and its outdoor units can be monitored.
Ø
4
Pushing
TEST
button returns the status to the usual display.