– 91 –
13
Digital Inverter
Installation Manual
EN-25
EN-26
No.
Cause
Display mode 1
Display mode 2
D800 D801 D802 D803 D804 D800 D801 D802 D803 D804
1
Normal
2
Discharge (TD) sensor error
3
Heat exchanger (TE) sensor error
4
Heat exchanger (TL) sensor error
5
Outside air temperature (TO) sensor error
6
Suction (TS) sensor error
7
Heat sink (TH) sensor error
8
Outdoor temperature sensor (TE/TS)
connection error
9
Outdoor EEPROM error
10
Compressor breakdown
11
Compressor lock
12
Current detection circuit error
13
Thermostat for compressor activated
14
Model data not set (on the service P.C.
board)
15
MCU-MCU communication error
16
Discharge temperature error
17
Abnormal power (open phase detected or
abnormal voltage)
18
Heat sink overheat
19
Gas leak detected
20
4-way valve reverse error
21
High pressure release operation
22
Outdoor fan motor error
23
Compressor driver short-circuit protection
24
Position detection circuit error in one-line
display
(
: OFF
: ON
: Flashing)
* The LEDs and DIP switches are
located on the lower left of the P.C.
board of the outdoor unit.
25
Ps sensor error
26
Ps drop down error
27
High pressure SW error
No.
Cause
Display mode 1
Display mode 2
D800 D801 D802 D803 D804 D800 D801 D802 D803 D804
SW800 SW801 SW806
SW802
SW803
LED
ON
1
2
3
4
ON
1
2
3
4
SW804
SW805
ON
1
2
3
4
ON
1
2
3
4
D805
D804
D803
D802
D801
D800
D805
D804
D803
D802
D801
D800
Enlarged view of
LEDs