Consider the wind direction during the
operational season of the air conditioner, and
install the unit so that the discharge port is set
at a right angle relative to the wind direction.
• When using an air conditioner under low outside
temperature conditions (Outside temp:-5 °C or
lower) in COOL mode, prepare a duct or wind
shield so that it is not affected by the wind.
Necessary Space for Installation
(Unit: mm)
Obstacle at rear side
Upper side is free
1.
Single unit installation
2.
Obstacles on both right and left sides
3.
Serial installation of two or more units
Obstacle also above unit
Strong wind
Strong wind
<Example>
Wind shield
Wind shield
Wind shield
150
or
mo
re
20
0 or
more
150 or
more
300 or
more
The height of the
obstacle should
be lower than
the height of the
outdoor unit.
150 or
more
300 or
more
300 or
more
300 or
more
The height of the obstacle should be
lower than the height of the outdoor unit.
200 o
r more
150 or
more
500 or
more
Obstacle in front
Above unit is free
1.
Single unit installation
2.
Serial installation of two or more units
Obstacle also at the above unit
Obstacles in both front and rear of unit
Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of the
unit, should be lower than the height of the outdoor unit.
Standard installation
1.
Single unit installation
2.
Serial installation of two or more units
Serial installation in front and rear
Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of the
unit should be lower than the height of the outdoor unit.
Standard installation
50
0 o
r
mo
re
1,00
0 or
more
1,
00
0 or
mo
re
1,000 or
more
150 or
mor
e
1,
000
o
r
mo
re
200
o
r
more
1,
00
0 or
mo
re
300 or
more
300 or
more
1,000 or
more
300 or
more
1,500 or
more
2,000 or
more
200 or
more