– 64 –
FILE NO. SVM-13010
Table 1. Setting data (CODE No. table (example))
DN
01
02
03
06
OF
10
11
12
13
14
19
1E
28
2A
2b
31
32
40
5d
60
C2
d0
d3
d1
F0
F1
F2
F3
F4
Item
Filter sign lighting time
Filter pollution leve
Central control address
Heating suction temperature shift
Cooling only
Type
Indoor unit capacity
System address
Indoor unit address
Group address
Louver type (wind direction adjustment)
Temperature range of cooling/heating
automatic SW control point
Power failure automatic recovery
Option/Abnormal input (CN70) SW
Thermo output SW (T10
)
Ventilation fan (standalone)
Sensor SW (Selection of static pressure)
Humidifier control (+ drain pump control)
High ceiling SW
Timer setting (wired remote controller)
Demand setting
(outdoor unit current demand)
Remote controller operation save function
Rotation number of the self-clean operation
Frost protection function
Swing mode
Louver fixing position (Flap No. 1)
Louver fixing position (Flap No. 2)
Louver fixing position (Flap No. 3)
Louver fixing position (Flap No. 4)
Setting data
Factory-set value
Depending on Type
0000: standard
0099: Not determined
0002: +2°C
(flooring installation type: 0)
0000: Heat pump
Depending on model type
Depending on capacity type
0099: Not determined
0099: Not determined
0099: Not determined
Depending on Type.
0003: 3 deg (Ts ± 1.5)
0000: None
0002: Humidifier
0000: Thermo ON
0000: Not available
0000: Body sensor
0003: Humidifier ON + Pump OFF
0000: Standard
0000: Available
0075: 75 %
0001: Enable
0001: 210ypm(at self-clean operation)
0000: None
0001: Standard
0000: Not fixed
0000: Not fixed
0000: Not fixed
0000: Not fixed
Table 2. Type: CODE No. 10
∗
1 EEPROM initial value on the P.C. board for indoor unit servicing
∗
2
CAUTION
<Model Name: RAV-SM
∗∗∗
UTP
∗
>
For the above models, set the CODE No. to “
” and the setting
data 0000 (initial) to “0001”.
Table 3.
Indoor unit capacity: CODE No. 11
∗
EEPROM initial value on the P.C. board
for indoor unit servicing.
Setting data
0001
*1 * 2
Type
4-way Cassette Type
Type name abb.
RAV-SM
∗∗∗
UTP
∗
Setting data
0000
∗
0006
0007
0009
0012
0015
0017
0018
Type
Disable
40
45
56
80
110
140
160
SVM-13010_051-106.indd 64
SVM-13010_051-106.indd 64
2/1/13 2:49 PM