– 33 –
FILE NO. SVM-13010
Alternate lighting
(0.5 sec.)
Alternate lighting
(0.5 sec.)
No.
12
Item
Louver control
(Continued)
Outline of specifications
<<Selection of Swing mode>>
• For the Swing mode, the following three types of modes are
selectable and settable by keeping Swing/Direction
SWING/FIX
button pushed for 4 seconds or more on the remote controller.
Standard (4 pieces: same phase) swing
→
Data: [0001 (At shipment)]
When Swing operation is selected, four louvers align at the
horizontal discharge position and then start the Swing
operation at the same time.
Dual swing
→
Data: [0002]
When operation is selected, the louvers of louver No. [01]
and [03] move to the horizontal discharge position, the
louvers of louver No. [02] and [04] move to the downward
discharge position and then start the Swing operation at
the same time.
Cycle swing
→
Data: [0003]
When operation is selected, the louver No. [01] moves to
the horizontal discharge position, [03] to the downward
discharge position, [02] and [04] to the middle position and
then start the Swing operation at the same time.
• Three types of the swing modes can be also selected and set
by the setup data of CODE No. (DN) [F0].
• In case of selecting the Swing mode, “Dual swing” or “Cycle
swing”, the following numerals is displayed at the center of
the remote controller screen for approx. 3 seconds when
SWING/FIX
button was pushed to select [SWING].
(No display for the standard swing)
<<Louver lock (Louver fix)>>
• For the air direction setup for each discharge port, the louver
position can be locked during the normal operation.
• An arbitrary air direction of an arbitrary louver can be
registered and set by keeping
UNIT
LOUVER
button pushed for
4 seconds or more on the remote controller.
• The louver lock can be set by registering the setup data to
CODE No. (DN) [F1] to [F4] according to the following table.
CODE No.
F1
F2
F3
F4
Objective louver No.
01
02
03
04
Setup data
0000: Release (At shipment)
0001: Horizontal discharge position
~
0005: Downward discharge position
Dual swing
Cycle swing
Remarks
Carry out setting
operation during stop of
the unit; otherwise the
unit stops operation.
The standard swing
performs the same
swing operation as the
present operation
(2 series).
For the setting opera-
tion, refer to [How to
set up type of the
swings] in Item “Setup
at local site/Others”.
Carry out setting
operation during stop of
the unit; otherwise the
unit stops operation.
SVM-13010_001-050.indd 33
SVM-13010_001-050.indd 33
2/1/13 10:59 AM
2/1/13 10:59 AM