Applicable Controls

REQUIREMENT

When the air conditioner is used for the first time, it will 
take some moments after the power has been turned on 
before the remote controller becomes available for 
operations: This is normal and is not indicative of trouble.
• Concerning the automatic addresses (The automatic 

addresses are set up by performing operations on the 
outdoor interface circuit board.)

 

While the automatic addresses are being set up, no 
remote controller operations can be performed. Setup 
takes up to 10 minutes (usually about 5 minutes).

• When the power is turned on after automatic address 

setup

 

It takes up to 10 minutes (usually about 3 minutes) for 
the outdoor unit to start operating after the power has 
been turned on.

Before the air conditioner was shipped from the factory, 
all units are set to [STANDARD] (factory default). If 
necessary, change the indoor unit settings.

 

The settings are changed by operating the wired remote 
controller.

* The settings cannot be changed using only a 

wireless remote controller, simple remote controller 

or group control remote controller by itself so install 

a wired remote controller separately as well.

„

Basic procedure for changing 
settings

Change the settings while the air conditioner is not 
working. 

(Stop the air conditioner before making 

settings.)

CAUTION

Set only the CODE No. shown in the following table: Do 
NOT set any other CODE No.
If a CODE No. not listed is set, it may not be possible to 
operate the air conditioner or other trouble with the 
product may result.

* The displays appearing during the setting process 

differ from the ones for previous remote controllers 

(AMT21E, AMT31E). (There are more CODE No.)

1

Push and hold 

 button and “TEMP.” 

 

button simultaneously for at least 4 
seconds. After a while, the display flashes 
as shown in the figure. Confirm that the 
CODE No. is [01].

• If the CODE No. is not [01], push 

 button to 

clear the display content, and repeat the 
procedure from the beginning. (No operation of 
the remote controller is accepted for a while 
after 

 button is pushed.)

 

(While air conditioners are operated under the 
group control, “ALL” is displayed first. When 

 is pushed, the indoor unit number 

displayed following “ALL” is the header unit.)

1

6

1

3

2

5

4

(* Display content varies with the indoor unit 

model.)

2

Each time 

 button is pushed, indoor 

unit numbers in the control group change 
cyclically. Select the indoor unit to change 
settings for.

The fan of the selected unit runs and the louvers 
start swinging. The indoor unit for change settings 
can be confirmed.

3

Specify CODE No. [

] with “TEMP.” 

 / 

 buttons.

4

Select SET DATA [

] with “TIME” 

 / 

 buttons.

5

Push 

 button. When the display changes 

from flashing to lit, the setup is completed.

• To change settings of another indoor unit, 

repeat from Procedure 

2

.

• To change other settings of the selected indoor 

unit, repeat from Procedure 

3

.

Use 

 button to clear the settings. To make 

settings after 

 button was pushed, repeat from 

Procedure 

2

.

6

When settings have been completed, push 

 button to determine the settings.

When 

 button is pushed, 

 flashes and 

then the display content disappears and the air 
conditioner enters the normal stop mode.

 

 (While 

 is flashing, no operation of the 

remote controller is accepted.)

„

Installing indoor unit on high 
ceiling

When the height of the ceiling to be installed exceeds 
3.5 m, adjustment of air volume is necessary.
Set up the high ceiling.
• Set according to the basic operation procedure 

 

(

1

 

 

2

 

 

3

 

 

4

 

 

5

 

 

6

).

• CODE No. in Procedure specifies [5d].
• Select [SET DATA] in Procedure from “List of 

installable ceiling height” in this Manual.

• For the CODE No. in Procedure 

3

, specify [5d].

• For the CODE No. in Procedure 

4

, select the SET 

DATA of ceiling height to be set up from the table on 
the below.

„

Filter sign setting

According to the installation condition, the filter sign 
term (Notification of filter cleaning) can be changed.

 

Follow to the basic operation procedure

 

(

1

 

 

2

 

 

3

 

 

4

 

 

5

 

 

6

).

• For the CODE No. in Procedure 

3

, specify [01].

• For the [SET DATA] in Procedure 

4

, select the SET 

DATA of filter sign term from the following table.

SET DATA

0000

Standard (Factory default)

3.5 m or less

0001

High ceiling 1

4.0 m or less

SET DATA

Filter sign term

0000

None

0001

150H

0002

2500H

(Factory default)

0003

5000H

0004

10000H

25-EN

26-EN

+00EH99878901_01EN.book  Page 13  Wednesday, April 13, 2011  9:38 AM

Содержание RAV-SM1104CT-E

Страница 1: ...anual English Indoor Unit Model name Ceiling Type RAV SM564CT E RAV SM804CT E RAV SM1104CT E RAV SM1404CT E AIR CONDITIONER SPLIT TYPE Installation Manual 00EH99878901_01EN book Page 1 Wednesday April 13 2011 9 38 AM ...

Страница 2: ...removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who...

Страница 3: ...outdoor unit Gloves to provide protection for electricians and from heat Warning indications on the air conditioner unit Warning indication Description WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING Moving parts Do not operate unit with grille removed Stop the unit before the servicing CAUTION High temperature parts You might get burned when ...

Страница 4: ...nstallation work ventilate the room immediately If the leaked refrigerant gas comes in contact with fire noxious gas may generate Use forklift to carry in the air conditioner units and use winch or hoist at installation of them Refrigerant piping Install the refrigerant pipe securely during the installation work before operating the air conditioner If the compressor is operated with the valve open...

Страница 5: ... installation tools are changed from those for the conventional refrigerant Accordingly the exclusive tools are required for the new refrigerant R410A For connecting pipes use new and clean piping designed for R410A and please care so that water or dust does not enter To Disconnect the Appliance from Main Power Supply This appliance must be connected to the main power supply by means of a switch w...

Страница 6: ...r when the humidity is over 80 condensation from the indoor unit will drip possibly causing damage to anything underneath In the case of the wireless type of system rooms with the inverter type of fluorescent lighting or locations exposed to direct sunlight The signals from the wireless remote controller may not be sensed Locations where organic solvents are being used The air conditioner cannot b...

Страница 7: ...Remote controller wire take in port Knockout hole A B C D SM56 type 910 855 Ø6 4 Ø12 7 SM80 type 1180 1125 Ø9 5 Ø15 9 SM110 SM140 type 1595 1540 Ceiling surface Hanging bolt Unit Within Installation of hanging bolt Consider the piping wiring after the unit is hung to determine the location of the indoor unit installation and orientation After the location of the indoor unit installation has been d...

Страница 8: ...taken out from the rear side Grooves Groove Side panel Right In case of taking pipe from left side Taking pipe from left side is applied only to the drain pipe The refrigerant pipe cannot be taken out from the left side Cut off the groove section with a metal saw or plastic cutter In case of taking pipe from upper side Taking pipe from upper side is applied only to the refrigerant pipe When taking...

Страница 9: ...nsulation Provide the area where the pipe connects to the indoor unit with proper heat insulation Improper heat insulation will cause condensation to form The drain pipe must be sloping downward at an angle of 1 100 or more and do not run the pipe up and down arched shape or allow it to form traps Doing so may cause abnormal sounds Restrict the length of the traversing drain pipe to 20 meters or l...

Страница 10: ...In case of taking pipe from the left side In case of taking pipe from the left side exchange the plug from left to right Push in the plug of which end is not sharp up to the end Drain pipe NO GOOD Refrigerant pipe Drain pipe Drain pan Attached drain hose Confirm that soft hose is pushed in up to the end of the drain pan Fit the attached hose band to the end of the hose lay down the knob and then t...

Страница 11: ... as listed in the table below Tightening torque of flare pipe connections Pressure of R410A is higher than that of R22 Approx 1 6 times Therefore using a torque wrench tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque Incorrect connections may cause not only a gas leak but also a trouble of the refrigeration cycle CAUTION Tight...

Страница 12: ...c shock or a fire CAUTION For power supply specifications follow the Installation Manual of outdoor unit Do not connect 220 240 V power to the terminal blocks for control wiring Otherwise the system will fail Do not damage or scratch the conductive core and inner insulator of power and inter connecting wires when peeling them Perform the electric wiring so that it does not come to contact with the...

Страница 13: ...ing Indoor power inter unit wiring Outdoor side Remote controller Remote controller wiring Indoor side Indoor Outdoor connecting wires Wire connection REQUIREMENT Connect the wires matching the terminal numbers Incorrect connection causes a trouble Pass the wires through the bushing of wire connection holes of the indoor unit Keep a margin Approx 100 mm on a wire to hang down the electrical contro...

Страница 14: ...a while after button is pushed While air conditioners are operated under the group control ALL is displayed first When is pushed the indoor unit number displayed following ALL is the header unit 1 6 1 3 2 5 4 Display content varies with the indoor unit model 2 Each time button is pushed indoor unit numbers in the control group change cyclically Select the indoor unit to change settings for The fan...

Страница 15: ...ift 0001 1 C 0002 2 C Factory default 0003 3 C 0004 4 C 0005 5 C 0006 6 C UNIT No 1 1 UNIT No 1 2 UNIT No 1 3 UNIT No 1 4 Setting of power level in power saving mode 1 3 4 2 3 Pushing left side of the button select an indoor unit to be monitored The sensor temperatures of indoor units and their outdoor unit in the control group are displayed 4 Push button to return to the normal display Group cont...

Страница 16: ...s Example of random setup After setup change of manual address Example of address setup change Outdoor unit Indoor unit Indoor unit Indoor unit Line address Group address Indoor address Address 1 1 1 Address 2 1 2 Address 2 2 2 Address 1 1 2 Address 2 1 2 Address 3 3 1 Procedure example 1 Single system Twin system Triple system Outdoor unit Indoor unit Indoor unit Indoor unit Remote controller Add...

Страница 17: ...o erase the display and repeat procedure from the first step After pushing button operation of the remote controller is not accepted for approx 1 minute 2 In the group control every time button is pushed the indoor UNIT No in the group control is displayed in order In this time the position of the indoor unit can be confirmed because only fan of the selected indoor unit operate For a group control...

Страница 18: ...ush button to stop a test run Display part is same as procedure 1 5 Push button to cancel release from the test run mode TEST disappears on the display and the status returns to a normal 2 4 3 1 5 Wireless remote controller 1 Push ON OFF button on the remote controller select COOL or HEAT with MODE button and then select HIGH with FAN button 2 Cooling test run Set the temperature to 18 C with temp...

Страница 19: ... and remove them or apply rustproof treatment if necessary As a general rule when an indoor unit is operated for 8 hours or more daily clean the indoor unit and outdoor unit at least once every 3 months Ask a professional for this cleaning maintenance work Such maintenance can extend the life of the product though it involves the owner s expense Failure to clean the indoor and outdoor units regula...

Страница 20: ...unit and outdoor unit Auto reset IPDU CDB communication error E08 Duplicated indoor addresses Indoor Indoor address setting error The same address as the self address was detected Auto reset E09 Duplicated header remote controllers Remote controller Remote controller address setting error Two remote controllers are set as header in the double remote controller control The header indoor unit stops ...

Страница 21: ... in the discharge temp releasing control Entire stop P04 ALT Outdoor unit high pressure system error Outdoor High pressure switch The IOL was activated or an error was detected in the high pressure releasing control using the TE Entire stop P05 ALT Open phase detected Outdoor The power wire may be connected incorrectly Check open phase and voltages of the power supply Entire stop P07 ALT Heat sink...

Страница 22: ...EH99878999 00EH99878901_01EN book Page 51 Wednesday April 13 2011 9 38 AM ...

Отзывы: