– 24 –
30°C
7.97
Procedure
Push the START/STOP button once to
set in operation mode.
1.Setting the anti-restart timer
2.Cooling operation
3.Fan speed: AUTO
4.Set the temperature sufficiently
lower than the room temperature.
5.Continuous operation
Connect the motor connector to
“MOTOR” and turn the power ON.
Start operation as follows:
1.Set the operation mode to “FAN
ONLY”.
2.Set the fan speed to “HIGH”.
3.Continuous operation
Trouble cause
• The temperature of the indoor
heat exchange unit is extremely
low.
• Defective control PC board.
• Indoor fan motor is failure.
• Contact of the motor connector is
defective.
• Main PC board is failure.
Check point (Symptom)
1. The compressor does not operate.
2. The OPERATION lamp flashes.
1. There is a voltage of 120V or more
between the red and black motor
connector leads.
2. The motor does not rotate. (But the
key operation of the remote control
is accepted.)
3. Motor rotates but vibrates hard.
10°C
20.7
20°C
12.6
0°C
35.8
(= k
Ω
)
Wireless remote controller
Timer short diode
•
Drill 2 holes on the rear of the wireless remote
control unit.
Attach the diode (1S1555 or equivalent) to the
rivet inside the unit.
•
Push the START/STOP button to start operation
with the diode attached.
•
During operation, push the trans mission/check
button while the diode is attached.
8-5-2. How to Reduce the Operation Time of the Anti-restart Timer
Table 8-8 Approximate value of the sensor (thermistor) resistance (T
A
, T
C
)
Fig. 8-3
Thermo Sensor
Temperature
Sensor