Function CODE No. (DN Code) table (includes all functions needed to perform applied control on site)
DN
Item
Description
At shipment
01
Filter display delay timer 0000: None
0002: 2500H
0004: 10000H
0001: 150H
0003: 5000H
0002 : 2500H
02
Dirty state of filter
0000: Standard
0001: High degree of dirt (Half of standard time)
0000: Standard
1E
Temp difference of
[AUTO] mode selection
COOL
→
HEAT,
HEAT
→
COOL
0000: 0 °C
to
0020: 20 °C
(For setup temperature, reversal of COOL / HEAT by } (Data value) / 2)
0003: 3 °C
(Ts ±1.5)
06
Heating temp shift
0000: 0 °C
0002: +2 °C
0001: +1 °C
0010: +10 °C
(Up to +6 recommended)
to
0002 : +2°C
2E
HA terminal (CN61)
select
0000: Usual
0002: Fire alarm input
0001: Leaving-ON prevention control 0000: Usual
(HA terminal)
2A
Selection of option/Trouble
input (TCB-PCUC2E: CN3)
0000: Filter input
0002: None
0001: Alarm input (Air washer, etc.) 0002: None
28
Automatic restart of
power failure
0000: None
0001: Restart
0000: None
11
Indoor unit capacity
0000: Unfixed
0001 to 0039
According to capacity
type
32 TA sensor selection
0000: Body TA sensor
0001: Remote controller sensor
0000: Body TA sensor
33 Temperature unit select 0000: °C (at factory shipment)
0001: °F
0000: °C
31 Ventilating fan control
0000: Unavailable
0001: Available
0000: Unavailable
0001 : 4-way Cassette
Type
10
0000 : 1-way Cassette to 0038
0001 : 4-way Cassette
0F
Cooling only
0000: Heat pump
0001: Cooling only (No display of [AUTO] [HEAT])
0000: Heat pump
0d
Existence of [AUTO]
mode
0000: Provided
0001: Not provided (Automatic selection from connected outdoor unit)
0000: Provided
04
Specific indoor unit
priority
0000: No priority
0001: Priority
0000: No priority
03
Central control address 0001: No.1 unit
0001: No.1 unit
00Un: Unfixed (When using U series remote controller)
0099: Unfixed (Other than U series remote controller)
0128: No.128 unit ... TU2C-Link
0064: No.64 unit ... TCC-Link
to
to
00Un/0099: Unfixed
*
1
12
Line address
0001: No.1 unit
0001: No.1 unit
00Un: Unfixed (When using U series remote controller)
0099: Unfixed (Other than U series remote controller)
0128: No.128 unit ... TU2C-Link
0030: No.30 unit ... TCC-Link
to
to
00Un/0099: Unfixed
*
1
13
Indoor unit address
0001: No.1 unit
0001: No.1 unit
00Un: Unfixed (When using U series remote controller)
0099: Unfixed (Other than U series remote controller)
0128: No.128 unit ... TU2C-Link
0064: No.64 unit ... TCC-Link
to
to
00Un/0099: Unfixed
*
1
14
Group address
0000: Individual
0002: Follower unit of group
00Un: Unfixed (When using U series remote controller)
0099: Unfixed (Other than U series remote controller)
0001: Header unit of group
00Un/0099: Unfixed
*
1
60
Timer setting
(wired remote controller)
0000: Available (can be performed) 0001: Unavailable
(cannot be performed)
0000: Available
5d
High-ceiling adjustment
(Air flow selection)
0000: Standard
- 80 -