– 10 –

Opening a ceiling and 
installation of hanging bolts

• Consider the piping / wiring after the unit is hung to 

determine the location of the indoor unit installation 
and orientation.

• After the location of the indoor unit installation has 

been determined, open the ceiling and install 
hanging bolts.

• The dimensions of the ceiling opening and hanging 

bolt pitches are given in the outline drawing and the 
attached installation pattern.

• When a ceiling already exists, lay the drain pipe, 

refrigerant pipe, control wires, and remote controller 
wires to their connection locations before hanging 
the indoor unit.

Procure hanging bolts and nuts for installing the indoor 
unit (these are not supplied).

Using the installation pattern (accessory)

The installation pattern is provided inside the 
packaging cap.

<For existing ceiling>

Use the installation pattern positioning a ceiling 
opening and hanging bolts.

<For new ceiling>

Use the installation pattern to position the ceiling 
opening when a ceiling is hanged.
• After the hanging bolts have been installed, install 

the indoor unit.

• After loosening the panel fixing screws of the indoor 

unit, hook them on the four holes in the installation 
pattern.

• When hanging a ceiling, open the ceiling along the 

outside dimensions of the installation pattern.

Treatment of ceiling

The ceiling differs according to structure of building. 
For details, consult your constructor or interior finish 
contractor.
In the process after the ceiling board has been 
removed, it is important to reinforce ceiling foundation 
(frame) and to keep horizontal level of installed ceiling 
correctly in order to prevent vibration of ceiling board.
1. Cut and remove the ceiling foundation.
2. Reinforce the cut surface of ceiling foundation, and 

add ceiling foundation for fixing the end of ceiling 
board.

Installation of hanging bolt

Use M10 hanging bolts (4 pcs, locally procured). 
Matching to the existing structure, set pitch according 
to size in the unit external view as shown below.

Hanging bolt

M10 or W3/8

4 pieces

Nut

M10 or W3/8

12 pieces

Indoor unit

Panel fixing

screw

Installation pattern

(Accessory)

Installation pattern 

attachment hole

New concrete slab

Install the bolts with insert brackets or anchor bolts.

Steel flame structure

Use existing angles or install new support angles.

Existing concrete slab

Use a hole-in anchors, hole-in plugs, or a hole-in bolts.

Rubber

Anchor bolt

(Blade type 

bracket)

(Slide type 

bracket)

(Pipe hanging 

anchor bolt)

Hanging bolt

Hanging bolt Support angle

Installation of ceiling opening and 
hanging bolt

• Attach a nut (locally procured) and the washer 

(supplied) to each hanging bolt.

• Insert a washer on both sides of the T groove of the 

hanging bracket of the indoor unit, and hang the 
indoor unit.

• Check that the four sides of the indoor unit are level 

using a level gauge (levelness: 5 mm or less).

• Detach the installation gauge (accessory) from the 

installation pattern.

• Using the installation gauge, check and adjust the 

positional relation between the indoor unit and the 
ceiling opening (1) (2.5 - 9.5 mm: 4 sides) and the 
hanging-up height (2) (23 - 28 mm: 4 corners).
(How to use the installation gauge is printed on the 
gauge.)

For the grid ceiling, incline the unit and then mount the 
unit from the electrical control box side as shown in the 
figure below.

CAUTION

CAUTION

Before installation of the indoor unit, remove the tape 
that holds the fan and bell mouth. Running the unit 
without removing the tape may damage the fan motor.

Hanging bolt

Level

Hanging bracket

Washer (Accessory)
To prevent the bolt 

from falling off (for 

safety), be sure to set 

it just under the 

hanging bracket as 

shown in the figure.

Eccentric washer 

(Accessory)

Nut M10 or

W3/8

Hanging bolt

M10 or W3/8

Nut

M10 or W3/8

* Procure hanging bolts 

and nuts locally.

* Install with the marking 

“UP” facing up.

Grid ceiling

Electrical control 

box side

Indoor unit

Level gauge (levelness: 5 mm or less)

Hanging bolt

Hanging 

bracket

Installation gauge

(1) 2.5 - 9.5 mm

Ceiling 

board

(2

23

 -

 2

8

mm

Indoor unit

Installation gauge

(2) 23 - 28 mm

Ceiling board

(1) 2.5 - 9.5 mm

19-EN

20-EN

Содержание RAV-HM301MUT-E

Страница 1: ...AIR CONDITIONER SPLIT TYPE Installation Manual R32 Indoor Unit Compact 4 Way type RAV HM301MUT E RAV HM401MUT E RAV HM561MUT E Model name For commercial use English ...

Страница 2: ...erant HFC R32 which does not destroy the ozone layer This indoor unit is for the R32 refrigerant Be sure to combine with an outdoor unit for the R32 refrigerant Product information of ecodesign requirements Regulation EU 2016 2281 http ecodesign toshiba airconditioning eu en Contents 1 Precautions for safety 3 2 Accessory parts 7 3 Selection of installation place 7 4 Installation 9 5 Drain piping ...

Страница 3: ... pertaining to this electrical work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge ...

Страница 4: ...t in water leakage electric shock or fire Do not use any refrigerant different from the one specified for complement or replacement Otherwise abnormally high pressure may be generated in the refrigeration cycle which may result in a failure or explosion of the product or an injury to your body Before opening the intake grille of the indoor unit or service panel of the outdoor unit set the circuit ...

Страница 5: ...r conditioner is running Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner otherwise it may cause imperfect combustion Appliance and pipe work shall be installed operated and stored in a room with a floor area larger than Amin m How to get Amin m Amin M 2 5 0 22759 h0 M is the refrigerant charge amount in appliance in kg h0 is the installa...

Страница 6: ...on using a solderless terminal etc Connection trouble in the places where the wire is connected in the middle may give rise to smoking and or a fire Electrical wiring work shall be conducted according to law and regulation in the community and Installation Manual Failure to do so may result in electrocution or short circuit Test run Before operating the air conditioner after having completed the w...

Страница 7: ...ossibly resulting in rupture injury or other trouble 1 Refer to the Definition of qualified installer or qualified service person This Air Conditioner has adopted a refrigerant HFC R32 which does not destroy the ozone layer As the R32 refrigerant is easily affected by impurities such as moisture oxidized film oil etc due to the high pressure be careful not to allow the moisture dirt existing refri...

Страница 8: ...lace where drained water will not cause any problem Avoid installing in the following places Place exposed to air with high salt content seaside area or place exposed to large quantities of sulfide gas hot spring The unit should be used in these places special protective measures are needed A restaurant kitchen where a lot of oil is used or place near machines in a factory Oil adhering to the heat...

Страница 9: ... 10 mm or more 200 200 15 or more 271 or more 1000 or more 271 or more 1000 or more 1000 or more An obstacle 15 or more 1 400 or more 560 or more 3 Check port 450 2 Check port 450 1000 or more Ceiling height Unit m When the height of the ceiling exceeds the distance of the item Standard 4 way in below table the warm air is difficult to reach the floor It is necessary to change the setup value of t...

Страница 10: ... to 594 13 to 20 Panel external dimension 620 13 to 20 13 to 20 Ceiling open dimension 580 to 594 Panel external dimension 620 External view Unit mm 23 5 0 146 191 320 214 256 93 40 132 173 257 70 53 193 154 146 8 3 12 184 ØA Ceiling open dimension 580 to 594 Bottom face of ceiling Wiring entry for remote control Unit external dimension 575 Refrigerant pipe connecting port Gas side Refrigerant pip...

Страница 11: ...ccording to size in the unit external view as shown below Hanging bolt M10 or W3 8 4 pieces Nut M10 or W3 8 12 pieces Indoor unit Panel fixing screw Installation pattern Accessory Installation pattern attachment hole New concrete slab Install the bolts with insert brackets or anchor bolts Steel flame structure Use existing angles or install new support angles Existing concrete slab Use a hole in a...

Страница 12: ...ireless type remote controller can be installed in the same room 7 m o r le s s 5 Drain piping CAUTION CAUTION Following the Installation Manual perform the drain piping work so that water is properly drained and apply a heat insulation so as not to cause a dew drop Inappropriate piping work may result in water leakage in the room and wet of furniture Piping Heat insulating material Require the fo...

Страница 13: ...6 mm or less Underside of ceiling Indoor unit 300 mm or less Rising up 850 mm or less After the electric work has finished pour water during COOL mode operation If the electric work has not yet finished pull out the float switch connector CN34 Red from the electrical control box and check draining by plugging the single phase 220 240 V power to the terminal blocks and If doing so the drain pump mo...

Страница 14: ...mm Liquid side 6 4 mm 6 4 mm Outside diameter size R32 or R410A tool used Conventional tool used 6 4 9 5 0 0 5 1 0 1 5 12 7 Outside diameter size A 0 0 4 6 4 9 1 9 5 13 2 12 7 16 6 B A Tightening connection CAUTION CAUTION Do not apply excessive torque Otherwise the nut may crack depending on the conditions Tightening torque of flare pipe connections Incorrect connections may cause not only a gas ...

Страница 15: ...re is connected in the middle may give rise to smoking and or a fire CAUTION CAUTION For power supply specifications follow the Installation Manual of outdoor unit Do not connect 220 240 V power to the terminal blocks for control wiring Otherwise the system will fail Do not damage or scratch the conductive core and inner insulator of power and system interconnection wires during peeling them Perfo...

Страница 16: ... units refer to the following table Remote controller wiring Wiring between indoor unit and outdoor unit 1 Figure below shows the wiring connections between the indoor and outdoor units and between the indoor units and remote controller The wires indicated by the broken lines or dot and dash lines are provided at the locally 2 Refer to the both indoor and outdoor unit wiring diagrams 3 The power o...

Страница 17: ...cable type and diameter Cord clamp can be attached on either right or left side When twin system are connected clamp two cables with one cord clamp Wire type Specification Cord clamping position Cabtyre cable 3 core stranded wire 2 5 mm Side D Cabtyre cable 4 core stranded wire 1 5 mm Side C Side D Space 8 5 mm Side C Space 4 mm Hook part Screws Cover of electrical control box CAUTION CAUTION 1 Ma...

Страница 18: ...p control change cyclically Select the indoor unit to change settings for The fan of the selected indoor unit runs and the louvers start swinging The indoor unit can be confirmed for which to change settings 3 Push OFF timer button to confirm the selected indoor unit 4 Push the menu button to make Code No flash Change Code No with setting button 5 Push the menu button to make Set data flash Change...

Страница 19: ...cur during cooling mode When the setting has been determined lights up Set data Detection temperature shift value 0000 No shift 0001 1 C 0002 2 C Factory default 0003 3 C 0004 4 C 0005 5 C 0006 6 C Set data Filter sign term 0000 None 0001 150 H 0002 2500 H Factory default 0003 5000 H 0004 10000 H Set data Swing of louvers 0001 Standard swing Factory default 0002 Dual swing 0003 Cycle swing 1 0001 ...

Страница 20: ...r Indoor unit Indoor unit Indoor unit Indoor unit Group control for system of multiple units One group can control up to 16 TU2C Link or 8 TCC Link indoor units with one remote controller Refer to the Wiring specifications Group control in single system For wiring procedure and wiring method of the individual line Identical refrigerant line system follow to Electrical connection Wiring between lin...

Страница 21: ...push the buttons 3 Push the ON OFF button return to the normal mode 9 Test run Before test run Before turning on the power supply carry out the following procedure 1 By using 500 V megger check that resistance of 1 MΩ or more exists between the terminal block 1 to 3 and the earth grounding work If resistance of less than 1 MΩ is detected do not run the unit 2 Check the valve of the outdoor unit be...

Страница 22: ...perature to 17 C with the temp setup buttons After confirming a signal receiving sound beep immediately set the temperature to 30 C with the temp setup buttons Monitoring function This function can be used to call the service monitor mode from the remote controller during a test run to obtain the temperature of the sensors of the remote controller indoor unit and outdoor unit 1 Push and hold menu ...

Страница 23: ...ay from the grille and remove Hook Fall preventive strap 4 Cleaning with water or vacuum cleaner If dirt is heavy clean the air filter using tepid water with a neutral detergent or just water After cleaning with water dry the air filter sufficiently in a shaded place 5 Mount the air filter 6 Close the air intake grille Check that the fall preventive strap of the air intake grille is attached to th...

Страница 24: ...st dirt appearance Replace the fan when vibration or balance is terrible Brush or wash the fan when it is contaminated Air intake discharge grilles Indoor outdoor Dust dirt scratches Fix or replace them when they are deformed or damaged Drain pan Indoor Dust dirt clogging drain contamination Clean the drain pan and check the downward slope for smooth drainage Ceiling panel louvers Indoor Dust dirt...

Страница 25: ...nsor TA indoor P C board Open circuit or short circuit of the room temp sensor TA was detected Auto reset F12 ALT TS sensor trouble Outdoor TS sensor may be displaced disconnected or short circuited Entire stop F13 ALT Heat sink sensor trouble Outdoor Abnormal temperature was detected by the temp sensor of the IGBT heat sink Entire stop F15 ALT Temp sensor connection trouble Outdoor Temp sensor TE...

Страница 26: ... may be gas leakage from the pipe or connecting part Check for gas leakage Entire stop P19 ALT 4 way valve trouble Outdoor Indoor 4 way valve indoor temp sensors TC TCJ An trouble was detected due to temperature drop of the indoor unit heat exchanger sensor when heating Auto reset P20 ALT High pressure protective operation Outdoor High pressure protection Entire stop P22 ALT Outdoor unit fan troub...

Страница 27: ...EB99847701 DH91308201 ...

Отзывы: