8-3. Table Inspection of outdoor unit main parts
No.
Parts name
Checking procedure
1
Compressor
(Model : DA150A1
T-
2
1
F)
Measure the resistance value of each winding by using the tester.
Position
Resistance value
Red – White
0.93
Ω
White – Black
Black – Red
Under 20°C
Red
White
Black
2
Fan motor
(Model : ICF-140-
A
43-
1
)
Measure the resistance value of each winding by using the tester.
Position
Resistance value
Red – White
21.00±1.05
Ω
White – Black
Black – Red
Under 20°C
Red
White
Black
FILE NO. SVM-18041