No.
Part name
Procedure
Remarks
7
Fan motor
1) Carry out works of 1 of
1
and
2
.
2) Take off the flange nut fixing the fan
motor and the propeller fan.
∗
The flange nut is loosened by turning
clockwise. (To tighten it, turn it
counterclockwise.)
3) Take off the propeller fan 2 pcs.
4) Take off the connector for fan motor
from the inverter.
5) Take off the fan motor lead from the fan
motor lead fixing rubber of the
penetrated part of the partition plate.
6) Take off the fixing screws (4 pcs. each)
while supporting the fan motor so that it
does not fall.
∗
Cautions when assembling the fan
motor
∗
Tighten the flange nut with 6.86N•m
(70kgf.cm).
∗
Adjust length on the fan motor lead
fixing rubber so that the fan motor
lead does not slacken in order not to
put the fan motor lead into contact
with the propeller fan.
Attach the fan motor lead fixing
rubber to the partition plate so that
projection directs to the refrigerating
cycle side.
∗
Be sure to bind the removed
bundling band with the bundling
band on the market.
CAUTION
Use the metal band of the motor base to
fix the fan motor lead on the motor base
so that the fan motor lead does not come
to contact with the propeller fan.
Loosened by
turning clockwise
Fan motor (Upper)
Propeller fan
Frange nut
Fan motor (Lower)
Fan motor (Upper)
lead fixing
rubber
Partition plate
Fan motor (Upper)
lead fixing
rubber
- 92 -