Check
code
Outdoor
LED display
Check and troubleshooting
(Item without special mention Indicates part of outdoor unit.)
[P26]
[Short-circuit of compressor drive element]
Correct wiring.
Replace outdoor P.C. board.
YES
NO
Does the same error occur in
operation without compressor lead?
Check compressor. (Rear short, etc.)
Defect
→
Replace
Are connections of
compressor lead and reactor correct?
(Check referring to the Wiring diagram.)
NO
YES
[P29]
[Position detection circuit error]
Check outdoor P.C. board.
Defect
→
Replace
—
No code
[Other error]
Compressor disorder due to sudden change of load, etc.
*
Although the display of outdoor LED outputs, the unit automatically restarts and
error is not determined.
*
LED display also may output due to wire coming-off of compressor.
- 74 -